CPS20.241-60
C-Series
24V,
400W,
DC/DC
C
ONVERTER
Sep. 2019 / Rev. 1.1 DS-CPS20.241-60-EN
All parameters are specified at 24.5V, 16.3A, 110Vdc, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/22
Fig. 4-3
Input current vs. output load
16
0
2
4
6
8
0
1
2
3
4
5A
Output Current
Input Current at 110Vdc input, typ.
10 12 14
18A
5.
I
NPUT
I
NRUSH
C
URRENT
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current
max.
13A
peak
at 110Vdc, temperature independent
typ.
6A
peak
at 110Vdc, temperature independent
Inrush energy
max.
1A
2
s
at 110Vdc, temperature independent
Fig. 5-1
Typical input inrush current behaviour at nominal load and
25°C ambient