Puls Dimension C Series Скачать руководство пользователя страница 20

 

 

CPS20.241-60 

 

 

 

 

C-Series 

24V,

 

400W,

 

DC/DC

 

C

ONVERTER

 

 

 

Sep. 2019 / Rev. 1.1 DS-CPS20.241-60-EN  

All parameters are specified at 24.5V, 16.3A, 110Vdc, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

20/22 

 

23.6.

 

P

ARALLEL 

U

SE TO 

I

NCREASE 

O

UTPUT 

P

OWER

 

CPS20.241-60 DC/DC converters can be paralleled to increase the output power as long as the ambient temperature 
stays below 60°C. 
Energize all units at the same time to avoid the overload Hiccup

PLUS

 mode. It also might be necessary to cycle the input 

power (turn-off for at least five seconds), if the output was in Hiccup

PLUS

 mode due to overload or short circuits and the 

required output current is higher than the current of one unit. 

 

 

Fig. 23-4

   Parallel use to increase the output power 

 

Instructions for parallel use: 

 

Unit A

Unit B

-

+

-

+

Load

+

-

Input

Output

Input

Output

 

 

-  Keep an installation clearance of 15mm (left / right) 

between two DC/DC converters and avoid installing the 
DC/DC converters on top of each other. 

-  Do not parallel DC/DC converters in orientations other 

than the standard mounting orientation (terminals on 
bottom of the unit) or in any other condition where a 
derating of the output current is required (e.g. altitude, 

temperature, input voltages). 

-  Pay attention that EMI and inrush current will increase 

when using multiple DC/DC converters. 

23.7.

 

P

ARALLEL 

U

SE FOR 

R

EDUNDANCY

 

CPS20.241-60 DC/DC converters can be paralleled for redundancy to gain higher system availability. Redundant systems 
require a certain amount of extra power to support the load in case one DC/DC converter unit fails. The simplest way is 
to put two DC/DC converters in parallel. This is called a 1+1 redundancy. In case one DC/DC converter unit fails, the 

other one is automatically able to support the load current without any interruption. Redundant systems for a higher 
power demand are usually built in a N+1 method. E.g. five DC/DC converter, each rated for 16A are paralleled to build 
a 64A redundant system. For N+1 redundancy the same restrictions apply as for increasing the output power, see also 
section 23.6. 
Since the CPS20.241-60 already has decoupling MOSFETS included, which cover failures such as an internal short circuit 
in the secondary side of the DC/DC converter, no additional redundancy modules are required. 

 

 

Fig. 23-5

   Redundant power design 

 

 

24V

20A

Load

+

-

PE

Failure

Monitor

PE

CPS20.241-60

24.5V 400W

Power

Supply

+  +

-  -

DC-

OK

Input

Output

+

-

I

I

PE

CPS20.241-60

24.5V 400W

Power

Supply

+  +

-  -

DC-

OK

Input

Output

+

-

 

 

Recommendations for building redundant power 
systems: 
-  Use separate input fuses for each

 

DC/DC 

converter. 

-  Monitor the individual DC/DC converter units.  

Use the DC-OK relay contact of the CPS20.241-60. 

Содержание Dimension C Series

Страница 1: ...these requirements the unit is equipped with conformal coated pc boards The unit features a DC OK signal contact for remote monitoring a decoupling MOSFET for building redundant power supply systems a...

Страница 2: ...eries 19 23 6 Parallel Use to Increase Output Power 20 23 7 Parallel Use for Redundancy 20 23 8 Series Operation 21 23 9 Back feeding Loads 21 23 10 Use in a Tightly Sealed Enclosure 21 23 11 Mounting...

Страница 3: ...ng orientations see de rating requirements in this document See chapter 23 11 This device is designed for convection cooling and does not require an external fan Do not obstruct airflow and do not cov...

Страница 4: ...nput voltage see Fig 4 3 Allowed voltage between input to earth ground max 375Vdc continuous IEC 62103 Allowed input ripple voltage max 15Vpp 3Vpp 50Hz 10kHz 10kHz 50kHz Turn on voltage typ 77Vdc stea...

Страница 5: ...nt Input Current at 110Vdc input typ 10 12 14 18A 5 INPUT INRUSH CURRENT An active inrush limitation circuit limits the input inrush current after turn on of the input voltage The charging current int...

Страница 6: ...max 11A average R M S current load impedance 50mOhm see Fig 6 2 Output capacitance typ 7 000 F included inside the DC DC converter HiccupPLUS Mode At heavy overloads when output voltage falls below 13...

Страница 7: ...avior definitions 0 20 40 60 100ms 70 90 110 130 150Vdc Input Voltage 80 Hold up Time at 16 3A typ at 8 2A min at 8 2A typ at 16 3A min 5 Hold up Time Output Voltage Input Voltage 8 DC OK RELAY CONTAC...

Страница 8: ...3A and 40 C 428 000h at 16 3A and 25 C MTBF SN 29500 IEC 61709 571 000h at 16 3A and 40 C 932 000h at 16 3A and 25 C MTBF MIL HDBK 217F 238 000h at 16 3A and 40 C Ground Benign GB40 322 000h at 16 3A...

Страница 9: ...terminals are IP20 finger safe constructed and suitable for field and factory wiring Shipped in open position Input and output DC OK Signal Type Bi stable quick connect spring clamp terminals push in...

Страница 10: ...ck as shown in Fig 12 2 Fig 12 1 Daisy chaining of outputs Fig 12 2 Using distribution terminals Load DC DC Converter Output DC DC Converter Output max 25A continuous Distribution Terminals Load DC DC...

Страница 11: ...iterion A Power Frequency magnetic field EN 61000 4 8 16 7Hz 50Hz 100A m Criterion A Power Frequency magnetic field EN 61000 4 8 0Hz 300A m Criterion A Pulsed magnetic field EN 61000 4 9 300A m Criter...

Страница 12: ...onverter in operation Shock 50g 30ms 3 bumps direction 18 bumps in total IEC 60068 2 27 DC DC converter not in operation Tests limits according to EN 61373 Altitude 0 to 2000m 0 to 6 560ft without any...

Страница 13: ...perature protection yes Output shut down with automatic restart Input transient protection MOV Metal Oxide Varistor Internal input fuse DC suitable fuse included not user replaceable Reverse input pol...

Страница 14: ...sting set the cut off current settings to the value in the table below Fig 18 1 Dielectric strength A B C D A D C B B Input DC ok Earth PE Output Type test 60s 2500Vac 3000Vac 1000Vac 500Vac Factory t...

Страница 15: ...th the following characteristics Altitude category AX EN 50125 1 4 2 1 Environmental category TX EN 50155 4 1 2 Interruption of voltage supply S2 EN 50155 5 1 1 2 Supply change over C2 EN 50155 5 1 3...

Страница 16: ...any 16 22 21 PHYSICAL DIMENSIONS AND WEIGHT Width 65mm 2 56 Height 124mm 4 88 Depth 127mm 5 0 The DIN rail height must be added to the unit depth to calculate the total required installation depth Wei...

Страница 17: ...the unit it is required that the black DIN rail slide on the back of the unit must be removed Instructions how to do this can be found in the manual of the ZM2 WALL 22 2 ZM13 SIDE SIDE MOUNTING BRACK...

Страница 18: ...one branch circuit the fuse or circuit breaker need a certain amount of over current to open in a timely manner This avoids voltage loss in adjacent circuits The extra current peak current is supplied...

Страница 19: ...are adapted to the wire size that is used the wiring is considered as thermally safe regardless of whether the MCB opens or not To avoid voltage dips and under voltage situations in adjacent 24V bran...

Страница 20: ...oltages Pay attention that EMI and inrush current will increase when using multiple DC DC converters 23 7 PARALLEL USE FOR REDUNDANCY CPS20 241 60 DC DC converters can be paralleled for redundancy to...

Страница 21: ...t Pay attention that EMI and inrush current will increase when using multiple DC DC converters 23 9 BACK FEEDING LOADS Loads such as decelerating motors and inductors can feed voltage back to the DC D...

Страница 22: ...ax allowed output current results in approximately half the lifetime expectancy of A1 Fig 23 7 Mounting Orientation A Standard orientation DC DC Converter OUTPUT INPUT Output Current 0 20 30 40 50 70...

Отзывы: