CPS20.241-60
C-Series
24V,
400W,
DC/DC
C
ONVERTER
Sep. 2019 / Rev. 1.1 DS-CPS20.241-60-EN
All parameters are specified at 24.5V, 16.3A, 110Vdc, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/22
3.
AC-I
NPUT
Do not operate this DC/DC converter with an AC-input voltage. Use the CPS20.241 or CPS20.241-C1 unit instead.
4.
DC-I
NPUT
Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not
recommended and can cause a malfunction or damage the unit.
Input voltage
nom.
DC 110V
-30%/+40%
Input voltage range
77-154Vdc
66-77Vdc
short term for 100ms
Input current
typ.
3.87A
at 16.3A and 110Vdc input voltage, see Fig. 4-3
Allowed voltage between input
to earth (ground)
max.
375Vdc
continuous, IEC 62103
Allowed input ripple voltage
max.
15Vpp
3Vpp
50Hz –10kHz
10kHz – 50kHz
Turn-on voltage
typ.
77Vdc
steady-state value, at ambient temperatures between
-20°C and +70°C, see Fig. 4-1
typ.
85Vdc
steady-state value, at -40°C ambient temperature
Shut-down voltage
typ.
60Vdc
steady-state value, see Fig. 4-1
Start-up delay
typ.
900ms
Rise time
typ.
85ms
at 16.3A constant current load, 0mF load capacitance,
see Fig. 4-2
typ.
130ms
at 16.3A constant current load, 20mF load capacitance,
see Fig. 4-2
Turn-on overshoot
max.
200mV
External input protection
See recommendations in chapter 23.3.
Fig. 4-1
Input voltage range
Fig. 4-2
Turn-on behavior, definitions
Tur
n-
on
77V
Rated
input range
max.
500ms
V
IN
P
OUT
375Vdc
154V
Shut
-down
Start-up
delay
Rise
Time
O
ve
rs
hoot
- 5%
Output
Voltage
Input
Voltage