CPS20.241-60 

 

 

 

 

C-Series 

24V,

 

400W,

 

DC/DC

 

C

ONVERTER

 

 

 

Sep. 2019 / Rev. 1.1 DS-CPS20.241-60-EN  

All parameters are specified at 24.5V, 16.3A, 110Vdc, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

1/22 

 

 

DC/DC

 

C

ONVERTER

 

 

EN 50155 Railway Compliant 

 

Conformal Coated PC-boards 

 

Built-in Redundancy (Decoupling Mosfet at the Output) 

 

Quick-connect Spring-clamp Terminals 

 

77-154Vdc Wide-range Input 

 

Width only 65mm 

 

Efficiency up to 93.7% 

 

Excellent Partial Load Efficiency 

 

Safe Hiccup

PLUS

 Overload Mode 

 

Minimal Inrush Current Surge 

 

Full Power Between -40°C and +70°C 

 

DC-OK Relay Contact 

 

Reverse Input Polarity Protected 

 

3 Year Warranty 

 
 

 

G

ENERAL 

D

ESCRIPTION

 

The CPS20.241-60 DC/DC converter is designed 
specifically for  railway & transportation applications. It 
is approved according to the EN 50155 standard, which 
is an international standard covering electronic 
equipment used on rolling stock for railway 

applications. The standard covers aspects such as 
temperature, humidity, shock, vibration, EMI and other 
parameters.  Because of these requirements,  the  unit  is 
equipped with conformal coated pc-boards. 

The unit features  a DC-OK signal contact for remote 
monitoring,  a  decoupling MOSFET for building 
redundant power supply  systems  and  quick-connect 
spring-clamp terminals for a reliable connection even 

when mechanical vibration and shock are involved. The 
unit also covers  an  extreme wide temperature range 
from -40°C up to +70°C with full output current. 

This DC/DC converter  comes in a very compact housing 
and requires only 65mm space on the DIN-rail due to 
the high efficiency and low power losses.  The  high 
efficiency  is achieved by utilizing cutting edge 
technology and other unique design techniques. 

 

S

HORT

-

FORM 

D

ATA

 

 

Output voltage 

DC 24.5V 

 

Adjustment range 

not adjustable 

Output current 

16.3A 

 

Output power 

400W 

 

Output ripple 

max. 100mVpp  20Hz to 20MHz 

AC Input voltage 

DC Input voltage 

DC 110V 

- 30%/ +40% 

DC Input current 

3.87A 

at 110Vdc 

Inrush current 

typ. 6A peak 

at 110Vdc 

Efficiency 

93.7% 

at 110Vdc 

Losses 

26.9W 

at 110Vdc 

Temperature range  -40°C to +70°C  operational 
Derating 

not required 

Hold-up time 

typ. 35ms 

at 110Vdc 

Dimensions 

65x124x127mm  WxHxD 

Weight 

980g / 2.16lb 

 

 

 

O

RDER 

N

UMBERS

 

DC/DC converter 

CPS20.241-60

   

Accessory 

  ZM2.WALL 

Wall mount bracket 

  ZM13.SIDE 

Side mount bracket 

 

M

ARKINGS

 

 

 

 

 

EMC, LVD

 

 

 

 

Содержание Dimension C Series

Страница 1: ...these requirements the unit is equipped with conformal coated pc boards The unit features a DC OK signal contact for remote monitoring a decoupling MOSFET for building redundant power supply systems a...

Страница 2: ...eries 19 23 6 Parallel Use to Increase Output Power 20 23 7 Parallel Use for Redundancy 20 23 8 Series Operation 21 23 9 Back feeding Loads 21 23 10 Use in a Tightly Sealed Enclosure 21 23 11 Mounting...

Страница 3: ...ng orientations see de rating requirements in this document See chapter 23 11 This device is designed for convection cooling and does not require an external fan Do not obstruct airflow and do not cov...

Страница 4: ...nput voltage see Fig 4 3 Allowed voltage between input to earth ground max 375Vdc continuous IEC 62103 Allowed input ripple voltage max 15Vpp 3Vpp 50Hz 10kHz 10kHz 50kHz Turn on voltage typ 77Vdc stea...

Страница 5: ...nt Input Current at 110Vdc input typ 10 12 14 18A 5 INPUT INRUSH CURRENT An active inrush limitation circuit limits the input inrush current after turn on of the input voltage The charging current int...

Страница 6: ...max 11A average R M S current load impedance 50mOhm see Fig 6 2 Output capacitance typ 7 000 F included inside the DC DC converter HiccupPLUS Mode At heavy overloads when output voltage falls below 13...

Страница 7: ...avior definitions 0 20 40 60 100ms 70 90 110 130 150Vdc Input Voltage 80 Hold up Time at 16 3A typ at 8 2A min at 8 2A typ at 16 3A min 5 Hold up Time Output Voltage Input Voltage 8 DC OK RELAY CONTAC...

Страница 8: ...3A and 40 C 428 000h at 16 3A and 25 C MTBF SN 29500 IEC 61709 571 000h at 16 3A and 40 C 932 000h at 16 3A and 25 C MTBF MIL HDBK 217F 238 000h at 16 3A and 40 C Ground Benign GB40 322 000h at 16 3A...

Страница 9: ...terminals are IP20 finger safe constructed and suitable for field and factory wiring Shipped in open position Input and output DC OK Signal Type Bi stable quick connect spring clamp terminals push in...

Страница 10: ...ck as shown in Fig 12 2 Fig 12 1 Daisy chaining of outputs Fig 12 2 Using distribution terminals Load DC DC Converter Output DC DC Converter Output max 25A continuous Distribution Terminals Load DC DC...

Страница 11: ...iterion A Power Frequency magnetic field EN 61000 4 8 16 7Hz 50Hz 100A m Criterion A Power Frequency magnetic field EN 61000 4 8 0Hz 300A m Criterion A Pulsed magnetic field EN 61000 4 9 300A m Criter...

Страница 12: ...onverter in operation Shock 50g 30ms 3 bumps direction 18 bumps in total IEC 60068 2 27 DC DC converter not in operation Tests limits according to EN 61373 Altitude 0 to 2000m 0 to 6 560ft without any...

Страница 13: ...perature protection yes Output shut down with automatic restart Input transient protection MOV Metal Oxide Varistor Internal input fuse DC suitable fuse included not user replaceable Reverse input pol...

Страница 14: ...sting set the cut off current settings to the value in the table below Fig 18 1 Dielectric strength A B C D A D C B B Input DC ok Earth PE Output Type test 60s 2500Vac 3000Vac 1000Vac 500Vac Factory t...

Страница 15: ...th the following characteristics Altitude category AX EN 50125 1 4 2 1 Environmental category TX EN 50155 4 1 2 Interruption of voltage supply S2 EN 50155 5 1 1 2 Supply change over C2 EN 50155 5 1 3...

Страница 16: ...any 16 22 21 PHYSICAL DIMENSIONS AND WEIGHT Width 65mm 2 56 Height 124mm 4 88 Depth 127mm 5 0 The DIN rail height must be added to the unit depth to calculate the total required installation depth Wei...

Страница 17: ...the unit it is required that the black DIN rail slide on the back of the unit must be removed Instructions how to do this can be found in the manual of the ZM2 WALL 22 2 ZM13 SIDE SIDE MOUNTING BRACK...

Страница 18: ...one branch circuit the fuse or circuit breaker need a certain amount of over current to open in a timely manner This avoids voltage loss in adjacent circuits The extra current peak current is supplied...

Страница 19: ...are adapted to the wire size that is used the wiring is considered as thermally safe regardless of whether the MCB opens or not To avoid voltage dips and under voltage situations in adjacent 24V bran...

Страница 20: ...oltages Pay attention that EMI and inrush current will increase when using multiple DC DC converters 23 7 PARALLEL USE FOR REDUNDANCY CPS20 241 60 DC DC converters can be paralleled for redundancy to...

Страница 21: ...t Pay attention that EMI and inrush current will increase when using multiple DC DC converters 23 9 BACK FEEDING LOADS Loads such as decelerating motors and inductors can feed voltage back to the DC D...

Страница 22: ...ax allowed output current results in approximately half the lifetime expectancy of A1 Fig 23 7 Mounting Orientation A Standard orientation DC DC Converter OUTPUT INPUT Output Current 0 20 30 40 50 70...

Отзывы: