CT10.241, CT10.241-C1
CT-Series
3-P
HASE
,
24V,
10A,
240W
May 2018 / Rev. 2.0a DS-CT10.241-EN All values are typical figures specified at 3x 400Vac, 50Hz input voltage, symmetrical
phase voltages, 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/28
Fig. 6-1
Output voltage vs. output current,
typ.
Fig. 6-2
Output voltage in “parallel use”
mode, typ.
Output Voltage
(Single Use, typ.)
0
0
9
18
4
8
12
28V
16
20
24
30A
21
12
3
6
15
24 27
Adjustment
Range
Output Current
Extra
current
for 20ms
Continuous
current
Factory
setting
Output Voltage
(Parallel Use, typ.)
22V
0
4
8
23V
24V
25V
29V
26V
27V
28V
12A
10
6
2
Adjustment
Range
Factory
setting
Output Current
7.
H
OLD
-
UP
T
IME
3AC 400V
3AC 480V
Hold-up Time
Typ.
34ms
54ms
At 24V, 10A, see Fig. 7-1
Typ.
68ms
108ms
At 24V, 5A, see Fig. 7-1
Min
28ms
44ms
At 24V, 10A, see Fig. 7-1
Min.
56ms
87ms
At 24V, 5A, see Fig. 7-1
Fig. 7-1
Hold-up time vs. input voltage
Fig. 7-2
Shut-down behavior, definitions
0
20
40
60
100ms
320
360
400
440 3x480Vac
Input Voltage
Hold-up Time at 24Vdc
5A
, ty
p.
10A
, typ.
10A,
min
.
5A, m
in.
80
- 5%
Hold-up Time
Output
Voltage
Input
Voltage
L1 L2 L3