CT10.241, CT10.241-C1
CT-Series
3-P
HASE
,
24V,
10A,
240W
May 2018 / Rev. 2.0a DS-CT10.241-EN All values are typical figures specified at 3x 400Vac, 50Hz input voltage, symmetrical
phase voltages, 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/28
14.
EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential,
commercial and light industry environments. The output is allowed to be grounded or floating.
The device is investigated according to the generic standards EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-
6-4.
Without additional measures to reduce the conducted emissions on the output (e.g. by using a filter), the
device is not suited to supply a local DC power network in residential, commercial and light-industrial
environments. No restrictions apply for local DC power networks in industrial environments.
EMC Immunity
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field
EN 61000-4-3
80MHz-2.7GHz
10V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
Output lines
4kV
2kV
Criterion A
Criterion A
Surge voltage on input
EN 61000-4-5
L1
L2, L2
L3, L1
L3
L1 / L2 / L3
PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output
EN 61000-4-5
+
-
+ / -
PE
500V
1kV
Criterion A
Criterion A
Conducted disturbance
EN 61000-4-6
0.15-80MHz
10V
Criterion A
Mains voltage dips
(Dips on three phases)
EN 61000-4-11
0% of 380Vac
0% of 480Vac
0Vac, 20ms
0Vac, 20ms
Criterion A
Criterion A
Mains voltage dips
(Dips on two phases)
EN 61000-4-11
40% of 380Vac
40% of 480Vac
70% of 380Vac
70% of 480Vac
200ms
200ms
500ms
500ms
Criterion A
Criterion A
Criterion A
Criterion A
Voltage interruptions
EN 61000-4-11
5s
Criterion C
Powerful transients
VDE 0160
Over entire load range
1550V, 1.3ms
Criterion A
Criterions:
A:
The device shows normal operation behavior within the defined limits.
C:
Temporary loss of function is possible. The device may shut down and restarts by itself. No damage or hazards for the device will occur.
EMC Emission
Conducted emission
input lines
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22
Class B
Radiated emission
EN 55011, EN 55022
Class B
Harmonic input current
EN 61000-3-2
Fulfilled for Class A equipment
Voltage fluctuations, flicker EN 61000-3-3
Fulfilled, tested with constant
current loads, non pulsing
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Switching Frequency
Main converter
60kHz to 140kHz
Output load and input voltage dependent