-15-
3.
Output power cable should be sized according to UPS size, do not use
undersized cabling. Please refer to Table 2
Model
Max. output current
Output cable
Terminal specification
1KVA
4A
12AWG
5.5-5
2KVA
7.5A
10AWG
5.5-5
3KVA
11A
10AWG
5.5-5
4KVA
15A
10AWG
5.5-5
6KVA
22A
10AWG
5.5-5
8KVA
30A
8AWG
8.5-6
10KVA
36A
8AWG
8.5-6
12KVA
44A
8AWG
16-6
15KVA
55A
6AWG
16-6
20KVA
72A
6AWG
16-6
Table 2
4.
Avoid short-circuit and overload.
5.
The comparison between output current rating and output cable size is
listed in Table 2.
6.
The ground to this unit only acts as reference point, if the grounding is
bad, that may cause disturbance and false management, and affect UPS
performance. Speak to professional personnel for assistance