-20-
5.
Utility indicator will be lit on when UPS input power source is
resumed. Press the LCD display cycle switch button to switch items
displayed, inspect if the display value is normal, thus first startup
procedure has been completed. Please measure output voltage and see
if it meets the requirement, then connect the load to the UPS output
terminal. Use pure power provided by UPS.
6.
After load is connected, press LCD display cycle switch button to
switch items displayed until it displays the output power percent %. If
the value displayed is more than 100%, please disconnect unimportant
load till the value displayed is less than 100%.
5.3
Operation process for routine turn-on/off
If you want to switch the UPS on or off, please operate the UPS
according to the following ways:
1.
You can switch off the UPS by pressing the “OFF’ button on front
panel. At this time the UPS is on bypass mode, output is utility
powered and the batteries are charged.
2.
Always turn on the UPS by pressing the “ON” button when in daily
operation.
5.4
Operation process if UPS is not in use
1.
If UPS is not used for more than ten days, please first turn off the UPS
by pressing the “OFF” button on front panel, then switch the power
switch NFB on the back panel to the “OFF” position.
2.
If UPS is not used for more than three months, please run the UPS for
more than 24 hours before the first start-up process and keep the
battery voltage level full to extend battery life.
Содержание GP800 Power Series
Страница 1: ...On line uninterruptible power supply User manual...
Страница 2: ......
Страница 6: ...2 environment 11 Do not leave objects on top of the UPS 12 Do not obstruct the air flow...
Страница 14: ...10 Figure 8 Figure 10 Figure 9...
Страница 30: ...26 Flow chart 1 of status handing...
Страница 31: ...27 Flow chart 2 of status handing...
Страница 32: ...28 Flow chart 3 of status handing Flow chart 3 of status handing...
Страница 33: ...29 Flow chart 4 of status handing...