-20-   

 

5.

 

Utility  indicator  will  be  lit  on  when  UPS  input  power  source  is 

resumed.  Press  the  LCD  display  cycle  switch  button  to  switch  items 

displayed,  inspect  if  the  display  value  is  normal,  thus  first  startup 

procedure has been completed. Please measure output voltage and see 

if  it  meets  the  requirement,  then  connect  the  load  to  the  UPS  output 

terminal. Use pure power provided by UPS. 

6.

 

After  load  is  connected,  press  LCD  display  cycle  switch  button  to 

switch items displayed until it displays the output power percent %. If 

the value displayed is more than 100%, please disconnect unimportant 

load till the value displayed is less than 100%. 

5.3

 

Operation process for routine turn-on/off 

If  you  want  to  switch  the  UPS  on  or  off,  please  operate  the  UPS 

according to the following ways: 

1.

 

You  can  switch  off  the  UPS  by  pressing  the  “OFF’  button  on  front 

panel.  At  this  time  the  UPS  is  on  bypass  mode,  output  is  utility 

powered and the batteries are charged. 

2.

 

Always  turn  on  the  UPS  by  pressing  the  “ON”  button  when  in  daily 

operation. 

5.4

 

Operation process if UPS is not in use 

1.

 

If UPS is not used for more than ten days, please first turn off the UPS 

by  pressing  the  “OFF”  button  on  front  panel,  then  switch  the  power 

switch NFB on the back panel to the “OFF” position. 

2.

 

If UPS is not used for more than three months, please run the UPS for 

more  than  24  hours  before  the  first  start-up  process  and  keep  the 

battery voltage level full to extend battery life. 

 

Содержание GP800 Power Series

Страница 1: ...On line uninterruptible power supply User manual...

Страница 2: ......

Страница 3: ...PLACEMENT NOTES 8 3 1 TRANSIT OR MOVE 8 3 2 PLACEMENT 8 4 INSTALLATION 11 4 1 INPUT 11 4 2 OUTPUT 14 4 3 DC INPUT WIRING 17 5 OPERATION PROCESS 18 5 1 PREPARATION BEFORE START UP 18 5 2 OPERATION PROC...

Страница 4: ...ENT MODES 30 7 1 UPS IN NORMAL MODE 30 7 2 UPS MODE WHILE UTITILTY POWER FAIL 30 7 3 UPS IN STATIC BYPASS MODE 31 7 4 BATTERY AND CHARGER 31 7 5 DAILY MAINTENANCE 32 8 COMMUNICATION INTERFACE 33 9 SPE...

Страница 5: ...l protection 1 3 Note The manual explains how to operate and maintain the system To optimize the use of the UPS please note the following 1 Read the manual carefully before use 2 Perform the operation...

Страница 6: ...2 environment 11 Do not leave objects on top of the UPS 12 Do not obstruct the air flow...

Страница 7: ...lay of input voltage value ON LINE AC IN 230V 4 Display of input frequency value ON LINE AC FRE 50Hz Figure 1 Symbol instruction of front panel indicator LCD Output indicator Fault indicator Battery e...

Страница 8: ...0 LED would display only after the unit is switched on These parameters vary with machine model 10 LCD cycle display switch button digital signal display items switch button 11 UPS switch button UPS...

Страница 9: ...terface Standard communication interface between UPS and computer 4 Power switch Power switch controls input output and battery power switch at the same time 5 Wiring terminal Power wiring terminal fo...

Страница 10: ...IFIER INPUT SWITCH When switched on the AC will be rectified 3 BATTERY INPUT SWITCH When turned on the battery begins to charge and discharges accordingly Switch position 1 3kva 192v 4 OUTPUT SWITCH o...

Страница 11: ...hed on the AC will be rectified 3 BATTERY INPUT SWITCH When turned on the battery begins to charge and discharges accordingly 4 OUTPUT SWITCH optional when turned on there is output power 5 MAINTENANC...

Страница 12: ...UPS while functioning 3 2 Placement 1 Do not place the UPS on a slope or uneven surface Figure 4 Figure 4 2 Place the UPS in a room where there is good ventilation The rear panel of UPS and two side f...

Страница 13: ...keep away from any fire source and high temperatures to avoid overheating Figure 8 5 Do not place goods on the UPS Figure 9 6 Do not install the UPS in places which contains caustic gasses Figure 10 7...

Страница 14: ...10 Figure 8 Figure 10 Figure 9...

Страница 15: ...e wires 3 Please connect UPS input terminal to utility power from a switchboard Figure 11 Note Do not swop live and neutral 4 Back panel position and connection 1 Remove two screws with screwdriver Fi...

Страница 16: ...Figure 13 6 Connect power correctly 1 Live L There is 220V relative to other two holes 2 Neutral N there is 220V relative to the Live there is 0 5 2V relative to the ground Load current circulate thr...

Страница 17: ...0AWG 5 5 5 4KVA 22 5A 10AWG 5 5 5 6KVA 31A 10AWG 5 5 5 8KVA 40A 8AWG 8 5 6 10KVA 50A 8AWG 8 5 6 12KVA 60A 6AWG 16 6 15KVA 72A 6AWG 16 6 20KVA 90A 4AWG 25 6 Table 1 9 The power cable and terminal must...

Страница 18: ...e the N cable of UPS is connected to utility neutral cable N the UPS GND is connected to the grounding club 15 If the model of the unit you purchased is 110V input please connect UPS L cable into line...

Страница 19: ...5 6KVA 22A 10AWG 5 5 5 8KVA 30A 8AWG 8 5 6 10KVA 36A 8AWG 8 5 6 12KVA 44A 8AWG 16 6 15KVA 55A 6AWG 16 6 20KVA 72A 6AWG 16 6 Table 2 4 Avoid short circuit and overload 5 The comparison between output...

Страница 20: ...ground close to the connecting point of the grounding club or origination point in the switchboard Please refer to figure 16 Please install wiring according to input voltage Contact an electrician or...

Страница 21: ...ry current Battery cable Terminal specification 1KVA 48Vdc 25A 12AWG 5 5 5 2KVA 48Vdc 50A 10AWG 5 5 5 3KVA 48Vdc 75A 10AWG 5 5 5 1KVA 6A 12AWG 5 5 5 2KVA 12A 10AWG 5 5 5 3KVA 18A 10AWG 5 5 5 4KVA 25A...

Страница 22: ...the input voltage meets the demand of the UPS 220V 10 with a meter 5 2 Operation process for first start up After verifying the above items are correct please turn on the UPS according to the followi...

Страница 23: ...ery four seconds which indicates the UPS runs on battery at present The sound will automatically stop 90s later UPS will sound alarm every 1s again when battery power is to be exhausted Figure 19 Figu...

Страница 24: ...less than 100 5 3 Operation process for routine turn on off If you want to switch the UPS on or off please operate the UPS according to the following ways 1 You can switch off the UPS by pressing the...

Страница 25: ...the UPS panel the LCD indicator and the LED lights will be as follows to indicate what mode the UPS is in 1 Panel indicator status 1 UPS running status Utility is normal UPS runs normal and UPS is us...

Страница 26: ...harging board Note the material parameters indicated may vary with the UPS Figure 25 Figure 24 Figure 23 LCD Output indicator Fault indicator Battery energy indicator Overload indicator Bypass indicat...

Страница 27: ...long beeps 2 Action to be taken Please remove load to ensure the percentage of LCD output power indicated is below 100 If the problem is still present after removing load please refer to flow Chart 3...

Страница 28: ...buzzer and indicator stop beep and flash 90s later 2 Action to be taken If utility is disconnected normally please remove non critical loads to increase used time If it is disconnected abnormally plea...

Страница 29: ...automatically 2 Action to be taken When utility power comes back UPS will automatically restart If utility power is disconnected for a long time above 6 hours please turn off UPS according to switch o...

Страница 30: ...26 Flow chart 1 of status handing...

Страница 31: ...27 Flow chart 2 of status handing...

Страница 32: ...28 Flow chart 3 of status handing Flow chart 3 of status handing...

Страница 33: ...29 Flow chart 4 of status handing...

Страница 34: ...the charger and keeps battery power at full voltage level while utility power is converted to DC power via the rectifier and is converted into pure sine wave power via the inverter feeding the load v...

Страница 35: ...ions 1 Overload 2 Inverter failure 3 During start up 4 When the inverter is switched off 5 UPS over temperature Inverter Rectifier Static Switch Filter Output Battery Charger Filter Input 7 4 Battery...

Страница 36: ...es fully charged to extend the battery life 7 5 Daily maintenance 1 UPS should be cleaned and maintained termly avoid any dust 2 Please clean UPS lightly with a soft cloth 3 Termly inspect all connect...

Страница 37: ...ing software such as WINDOWS LINUX NOVELL etc When utility power is disconnected the UPS notifies via the software that there is a utility fault and send out alarm information A predetermined time can...

Страница 38: ...34 4 Serial cable RS232 appearance figure 38 The pinout of RS232 is PIN2 RS232 RXD PIN3 RS232 TXD PIN5 GND Figure 38 5 Dry contact optional Common Fault AC fail Bypass Low BAT Common Figure 37...

Страница 39: ...al pin 4 and pin 1 are closed when AC abnormal pin 4 and pin 1 are closed whereas pin 5 and pin 1 are open 4 Bypass pin 6 is NO type contact pin 7 is NC type contact When UPS works normally pin 6 and...

Страница 40: ...tion 3 linear load Transient response 4 100 load 0 load Battery Voltage 48VDC 192VDC 192VDC Rated charging current Standard 1 2A long run 6A 12A optional Model Maintenance free lead acid battery Runti...

Страница 41: ...power by utility LCD display input output voltage frequency battery voltage output power temperature Battery BVL One LED on when battery low voltage UPS status indicator light Utility inverter bypass...

Страница 42: ...38 10 Shipping list Order Consent Number 1 UPS 1 2 UPS user manual 1 3 Intelligent monitoring software 1 4 RS232 Computer port cable 1...

Отзывы: