-23-
6.
Panel indicator status:
(1)
UPS running status:
Utility power is normal and it
converts to utility mode. UPS
will not start-up unless the
“ON” button is pushed down
on the UPS panel.
(2)
Action to be taken:
Refer to status dealing flow
Chart 2.
7.
Panel indicator status:
(1)
UPS running status:
Utility supplies power.
Under overload 125%,
overload indicator is lit on
and the buzzer long beeps.
(2)
Action to be taken:
Please remove load to ensure
the percentage of LCD
output power indicated is
below 100%. If the problem
is still present after removing load,
please refer to flow Chart 3
of status handling.
Figure 26
Figure 27
LCD
O utput indicator
Fault indicator
Batte ry energy indicator
O ver load indic ator
Bypass indica tor
Switch ON
Switch OFF
C ycle display botton
Input indicator
LCD
O utput indicator
Fault indicator
Batte ry energy indicator
O ver load indic ator
Bypass indica tor
Switch ON
Switch OFF
C ycle display botton
Input indicator
C urrent Lo ad
1 2 5% 7/8