-13-
(3)
Ground (G): Connect correctly to ground in the switchboard.
7.
If the difference between the neutral and the ground is more than 2V
or it cannot meet the requirements, please reinstall good grounding to
ensure safety of UPS operation.
8.
The comparison list of input current rating and input cable size is as
follows:
Model
Max. input
Input wire
Terminal specification
1KVA
8.5A
12AWG
5.5-5
2KVA
14A
10AWG
5.5-5
3KVA
17.5A
10AWG
5.5-5
4KVA
22.5A
10AWG
5.5-5
6KVA
31A
10AWG
5.5-5
8KVA
40A
8AWG
8.5-6
10KVA
50A
8AWG
8.5-6
12KVA
60A
6AWG
16-6
15KVA
72A
6AWG
16-6
20KVA
90A
4AWG
25-6
Table 1
9.
The power cable and terminal must be a first-grade product
manufactured by an authentic manufacturer.
10.
Do not wrap the power cables around the terminal block screws.
11.
After fastening the input cable, to avoid short-circuit, please see if the
input cable contacts properly and does not touch other wiring.
12.
Follow the electrical laws when doing installation.
13.
Avoid using the same
circuit breaker with other equipment when
connecting to the switchboard.
Содержание GP800 Power Series
Страница 1: ...On line uninterruptible power supply User manual...
Страница 2: ......
Страница 6: ...2 environment 11 Do not leave objects on top of the UPS 12 Do not obstruct the air flow...
Страница 14: ...10 Figure 8 Figure 10 Figure 9...
Страница 30: ...26 Flow chart 1 of status handing...
Страница 31: ...27 Flow chart 2 of status handing...
Страница 32: ...28 Flow chart 3 of status handing Flow chart 3 of status handing...
Страница 33: ...29 Flow chart 4 of status handing...