background image

 

+3V 

SB1 

SB2 

COM 

SEN3 

SEN2 

REF 

Optional remote functions 
PFC-ALV-RS and PFC-MLV-RS models ONLY  

Remote Setback 

Terminal Block 

Remote Sensor 
Terminal Block 

Remote Sensor/Aquastat Option: 

The remote sensor option features a dual mode external sensor 
function.  SEN2 is to be used only as a room temperature sensor 
(order PSG 

P-RS

).  SEN3 is to be used only with the Electronic 

Aquastat Kit (order PSG 

P-AK

).  The REF terminal is common to 

both sensor inputs.  To activate the SEN2 or SEN3 terminals see 
programming instructions.  Both sensor functions may be used at 
the same time, having both electronic aquastat and remote room 
temperature capability.  When the remote sensor is connected, it 
may be used to control the thermostat instead of the on board 
sensor or it may be averaged with the on board sensor.  Use only 
3 conductor cable or shielded 2 conductor cable.  Connect the 
shield or the third wire to the COM terminal.  

Remote Setback/Shutdown Option: 

The remote setback features a dual mode function.  SB1 is the input 
for remote setback (economy) and SB2 is the input for remote 
shutdown mode.  

Setback mode

 when energized will remotely 

place the thermostat in economy mode using the programmable 
economy heat and cool setpoints.  

Shutdown mode

 when energized 

will remotely place the thermostat in disable mode.  The thermostat, 
at this time, will not call for heating or cooling until taken out of shut- 
down mode. 
To activate the setback or shutdown mode use dry contacts (relays 
or mechanical switch) to connect the +3V terminal to the appropriate 
SB1 or SB2 terminal.  An open circuit on SB1 or SB2 will disable the 
remote function.   
 
A COM terminal is provided for active type remote switch gear such 
as the electronic motion sensor.  Do not use the COM terminal for 
any other application.   

+3V 

SB1 

SB2 

COM 

door  
switch 

window 
switch 

Dry contact connections 

+3V 

SB1 

SB2 

COM 

window 
switch 

(-) 

(+3vdc) 

Motion Sensor and dry contact 

Motion 
Sensor 

 

 

Mount the Electronic Aquastat Sensor to the water pipe.  The best 
location is to be as close to the main pipe as possible and attached 
before the water valve connection.  

IMPORTANT:

The electronic aquastat sensor replaces the bimetal switch
which is common in most 2-pipe heat/cool fan coil systems.
This allows for the thermostat to directly control the equipment 
as well as provide for alterations in change-over temperature 
thresholds.  Follow the standard 4-pipe wiring diagram. Cool 
wire will control the heat/cool valve,  the heat wire will operate 
as an auxilliary electric heat switch (depending on fan coil 
equipment).
Isolate all of the unused wires.

Water

Main

Valve

Sensor

Wire
Ties

 

 

 

Refer to the programming instructions for selecting the aquastat
sensor function, temperature changeover settings, output configurations, 
purge frequency and purge time duration.  The thermostat will monitor 
pipe temperature every 5 seconds.  For a valvelss systems,  select 
the 

2Pn

 configuration setting since this will bypass the valve purge 

functions and provide heating or cooling based on pipe temperature 
alone.   
The 

2PS

 and 

2PE

 configurations operate with a valve purge function

to prevent incorrect temperature readings from static or standing water 
in the pipe.  The valve purge operates on a programmed interval
(purge frequency) for a programed duration (purge time duration)
in the event of low activity over an extended period of time.  
If the heat or cool call has lasted for more than three minutes,  the 
pipe temperature heat or cool mode is rechecked to verify proper 
operating mode.

          

 

 

Function charts on next page

SEN3 

SEN2 

REF 

 

Room 
Sensor 

Aquastat Sensor 

+3V 

SB1 

SB2 

COM 

 

 

 

Отзывы: