TROUBLE SHOOTING TESTS (4-Pipe System)

Voltage:

 When using a voltmeter across "Black" and "Red" and  

 

  “Black” to “Orange”, voltage must be 24VAC.  

To Check Continuity:

  (Using a Voltmeter with all loads connected)

A)

  When the thermostat is calling for Cooling, meter should read  

 

 

24VAC from “Black” to “Yellow”.  When cooling is deactivated,  

 

 

meter should read 0VAC from “Black” to “Yellow”.

B)

  When the thermostat is calling for Heating,  meter should read  

 

 

24VAC from “Black” to “White”.  When heating is deactivated,  

 

 

meter should read 0VAC from “Black” to “White”.

C)

  When the thermostat is calling for High Fan,  meter should read    

 

24VAC from “Black” to “Violet”.  When all fan speeds are turned    

 

off,  meter should read 0VAC from “Black” to “Violet”. 

D)

  When the thermostat is calling for Medium Fan, meter should read    

 

24VAC from “Black” to “Blue”.  When all fan speeds are turned off,    

 

meter should read 0VAC from “Black” to “Blue”. 

E)

  When the thermostat is calling for Low Fan,  meter should read  

 

 

24VAC from “Black” to “Green”.  When all fan speeds are turned  

 

 

off, meter should read 0VAC from “Black” to “Green”.

2-PIPE FAN COIL INSTALLATION: (Bimetal Aquastat ONLY)
NOTE:  

For Electronic Aquastat applications (RS models) use the

4-Pipe wiring ONLY.
Follow the instructions for a 4-pipe installation with the following 
exceptions:

Old Thermostat 

Function 

Control Feed 

Common 

Water Valve 

Aquastat Heat 
Aquastat Cool 

Low Fan 

Medium Fan 

High Fan 

 

Cable Wire

 Color 

New Stat Wire 

Function 

Control Feed 

Common 

Load Feed (valve) 

Aquastat Heat 
Aquastat Cool 

Low Fan 

Medium Fan 

High Fan 

New Stat Wire 

Color 

Red 

Black 

Orange 

White 

Yellow 

Green 

Blue 

Violet 

Cable Wire Color 

NOTE:

  When the thermostat is programmed for 2 speed the High fan  

wire will not be used.  Also, when the thermostat is programmed for  
single speed fan, only the low fan wire connection will be used.  Isolate 
any unused fan speed wires from the thermostat.  

+3V 

SB1 

SB2 

COM 

SEN3 

SEN2 

REF 

+3V 

SB1 

SB2 

COM 

+3V 

SB1 

SB2 

COM 

 

 

 

 

9510-0712
Rev D    10-23-07

HEAT/AUT

O/COO

°F/°C 

SETPOINT 

AUTO 

Check Cooling:
 

Press and hold the down button until the cool 

  symbol appears on the LCD.  Within 4 seconds 
  the cool valve will be activated.  For manual
  changeover models place the system mode 
  switch in the cool or auto position.  
 

Note:

  Room temperature must be above 

  the Comfort Cooling Limit 65°F (18.5°C)
  for cooling to become active.

Adjust setpoint as follows: 

6.0°F or more ABOVE room temperature 

3.0°F to 5.9°F ABOVE room temperature 

0.4°F BELOW to 2.9°F ABOVE room temperature 

1.9°F to 0.4°F BELOW room temperature 

2.0°F BELOW room temperature (cool threshold) 

Heating Currently Active 

FUNCTION CHART 

MED 

Lo 

Hi Med 

Lo 

Med Med 

Lo Med 

Lo 

Off Med 

Lo Med 

HIGH 

Hi 

Hi 

Hi 

Hi 

Hi 

Lo 

On 

On 

On 

Off 

Reset Set 

LOW 

AUTO 

COOL 

HEAT 

FAN SPEED 

SYSTEM 

Lo 

Adjust setpoint as follows: 

2.0°F ABOVE room temperature 

1.9°F ABOVE to 1.9°F BELOW room temperature 

2.0°F BELOW room temperature 

Heating or Cooling Not Currently Active 

MED 

Lo 

Lo Med 

Lo 

Off Med 

Lo Med 

HIGH 

Hi 

Hi 

Hi 

Set 

Off Off 

Set 

LOW 

AUTO 

COOL 

HEAT 

FAN SPEED 

SYSTEM 

Lo 

Adjust setpoint as follows: 

2.0°F ABOVE room temperature (heat threshold) 

1.9°F to 0.4°F ABOVE room temperature 

0.4°F ABOVE to 2.9°F BELOW room temperature 

3.0°F down to 5.9°F BELOW room temperature

6.0°F or more BELOW room temperature 

Cooling Currently Active 

MED 

Lo 

Lo Med 

Lo 

Off Med 

Lo Med 

Lo 

Med Med 

Lo Med 

HIGH 

Hi 

Hi 

Hi 

Hi 

Hi 

Hi 

Set Reset 

Off 

On 

On 

On 

LOW 

AUTO 

COOL 

HEAT 

FAN SPEED 

SYSTEM 

Lo 

 

SEN3 

SEN2 

REF 

+3V 

SB1 

SB2 

COM 

 

 

 

Red

Wiring Diagram 2-pipe
Fan Coil with 3 Speed Fan

24VAC

Black

Green  LOW

Blue  MEDIUM

Violet  HIGH

Orange

Yellow

White

Fan

Valve

Common

Feed

Aquastat (mounted on water
supply line) or season change
switch

Red

Wiring Diagram 2-pipe
Fan Coil with 2 Speed Fan

24VAC

Black

Green  LOW

Blue  MEDIUM

Violet  NOT USED

Orange

Yellow

White

Fan

Valve

Common

Feed

Aquastat (mounted on water
supply line) or season change
switch