The table below represents the cycle time (operating time) per different Actuator sizes:
Table 6.
Operating Speed
Cycle time in seconds
Actuator
size
Spring-Return(12springs)
Double-Acting
0°-90°
90°-0°
0°-90°
90°-0°
PA32
N/A
N/A
0.5
0.4
PA40
N/A
N/A
0.55
0.47
PA52
2.66
0.44
0.6
0.53
PA63
2.74
0.52
0.66
0.58
PA75
2.83
0.61
0.72
0.64
PA83
3.01
0.74
0.83
0.73
PA92
3.26
0.79
1
0.86
PA105
4.36
1.08
1.35
1.3
PA125
4.68
1.22
2.4
1.79
PA140
4.84
1.65
2.5
2.1
PA160
5.83
3.4
3.93
2.6
PA190
8.5
4.5
4.55
3.45
PA210
17
4.84
5.5
4.35
PA240
18.4
6.14
8.4
8.33
PA270
24.9
12.54
10.9
8.53
PA300
31.6
16.54
15
14.9
Operating time is average with actuator under load and solenoid valve fitted.
Test conditions:
ϭ͘
Solenoid with flow capacity:
0.6 m
3
/hr
Ϯ͘
Pipe diameter:
6mm
ϯ͘
Medium:
clean air
ϰ͘
Supply pressure:
5.5 bar (80psi)
ϱ͘
Load:
with average load
ϲ͘
Stroke:
90°
ϳ͘
Temperature:
Room temperature
ϰ͘ϯ͘Ϯ
Ingress Protection (IP) rating
A210-211-212-213 Series actuators are IP66/IP67 rated. In case of IP66 or IP67
requirements, take precautions that comply with the IP66/IP67 requirements to prevent
moisture or dust from entering the actuator through the open air exhaust port(s), either
directly on the actuator or at the exhaust ports of the connected solenoid valve.
We recommend to connect tubing to the exhaust(s) and lead this into a dry and dust free
area, or to use check valves in the exhaust.