Code Parameter
Units Description
Factory
setting
Possible to
change?
d.28
Relay 2 function
(This is the second relay of the option
card)
-
Attributing a function to relay 2 of the option card:
1 = not applicable to this product
2 = auxiliary heating pump
4 = kitchen hood
5 = external gas valve
6 = external error message
2
yes
d.29 Unused
d.35
Position of 3-way valve (heating / DHW)
100 = domestic hot water
0 = heating
40 = centre position
-
read only
d.36
DHW flow rate
l/min
Flow rate measured by the hot water flow sensor
-
read only
The following menu is displayed if a solar system is connected to the appliance
d.39 Solar circuit inlet temperature
°C
Displays the temperature measured by the sensor located
on the solar circuit inlet.
-
read only
d.40
Heating flow temperature
°C
Displays the heating output temperature.
-
read only
d.41 Heating return temperature
°C
Displays the heating return temperature.
-
read only
Menus d.43, d.45 and d.47 only display if a wired outdoor thermostat is connected to terminal X17 of the main circuit board.
d.43 Heating curve
Choice of heating curve depending on the outside
temperature (see detail on following page)
1.2
yes
d.44 Ionisation check
Coef.
from
0 to
1000
The lower this value (burner lit), the better the detection.
However, this value depends on several parameters (gas
quality, electrodes...).
This value is without units : it’s just an indication.
-
read only
d.45 Heating curve base
°C
(See details, following page). Disappears for TA e-bus
20
yes
d.47 Outdoor temperature
°C
Displays the temperature measured by the outdoor sensor
-
read only
d.52 Offset for minimum steppermotor
position
Pmin adjustment . To adjust, see «Gas conversion» some
pages after.
yes
d.53 Offset for maximum steppermotor
position
Pmax adjustment . To adjust, see «Gas conversion» some
pages after.
yes
d.62
Night-time offset
(Specific function for Belgium and NL :
RT doesn’t stop the burner but
change the set-point.
Don’t use in
other countries
)
°C
Lowers the heating start temperature depending on
the state of TA 24V
E.g.: if d62 is set at 20, Setting= 65 °C if TA 24V on
Setting = 65 - 20 °C with TA 24V off
0 = function deactivated. Keep to 0 out of BE / NL.
0
yes
0 to 30°C
d64
Average burner ignition time
S
For these 2 values, an average calculated over the last 100
ignitions.
0
read only
d65
Max. burner ignition time
S
read only
d66
Warmstart
0 = Warmstart activated
1 = Warmstart de-activated
1
yes
d.67 Time remaining until the end of the anti-
short cycle delay.
min.
Displays time remaining until the end of the anti-short cycle
delay.
-
read only
d68
Number of ignitions failed on the first
attempt
-
0
read only
d69
Number of ignitions failed on the second
attempt
-
0
read only
The values with a green background are only accessible from the After-Sales menu (access code = 35)