Safety devices for open flue boilers
Temperature safety
(ant-freezing / overheating)
Gas safety valve
(EVS)
Smoke overflow
Flame control
3-way valve
anti-blockage
Water pressure sensor
Safety
Control device
Values
Action
Safety devices locking the appliance and requiring a RESET in the case of a fault
Overheating and
temperature limiting
Outgoing/return
heating NTC
97 °C => max. temperature
Fault displayed F20
T° increase more than 10 K/S.
Fault displayed F24
ΔT (outlet - return) > 35 K
Fault displayed F23
Flame control
Ignition and ionisation
electrode
Up to 2 spark sequences separated
by 7 seconds
Fault F28 if no ignition
Fault F29 if burner goes out
Gas
Gas safety valve
0V when shut down
24V then 16V in operation
Display of various faults depending
on origin
Smoke overflow
ON / OFF thermostat
23 and 25 kW appliances : contact
opens at 65°C
12 kW appliances : contact opens at
60°C.
Fault displayed F25
Safety devices not requiring a RESET after the fault clears
Antifreeze
Outlet NTC
7 °C --> immediate heating
Burner lit up to 35°C
Pump anti-blocking
Internal computer
Activated for 30s if not activated for
24 hours
Activation without apparent demand
3-way valve
anti-blockage
Activated for 30s if not activated for
24 hours
Activation without apparent demand
Heating pressure
Pressure sensor
Triggered at 0.5 bar
Reset at 0.3 bar
Display
below 0.3 bar
display blinking between 0.3 and 0.5 bar
Heating valve
Opens at 3 bar
Evacuation of excess pressure
(display blinking below 2.5 bar)
Pressure relief valve
(3 bar)
Pump anti-block