41
T
ROUBLESHOOTING
E Operating Manual with Troubleshooting Guide
www.protecta.hu
Table 5-6 CDSP error messages
E
RROR MESSAGE
(CDSP)
E
XPLANATION
0x0001 (System)
Critical system error. Corrupted file or
hardware error possible. The system cannot
operate reliably.
0x0002 (Config)
Critical configuration error, inconsistency or
internal structural problem. The system cannot
operate reliably.
0x0004 (Param)
Critical parameter error or data inconsistency
on the CDSP or RDSP.
0x0020 (TCP communication)
TCP communication system error. Hardware or
other system error possible.
0x0080 (File I/O)
File system error. The device cannot generate
the RDSP log.
0x0100 (RDSP comm. error)
RDSP communication problem. Software
inconsistency or hardware error possible.
Table 5-7 Hardware Init error messages
E
RROR MESSAGE
(HW
I
NIT
)
E
XPLANATION
0x0004 (FRAMError)
FRAM failure indicating CPU HW error.
0x0008 (extRTCError)
Real Time Clock reset generator failure
indicating CPU HW error.
0x0010 (sramError)
SRAM test failed at power up indicating CPU
HW error.
0x0020 (codeFlashError)
Flash IC no. 13 failed on the CPU module
indicating CPU HW error.
0x0040 (dataFlashError)
Flash IC no. 14 failed on the CPU module
indicating CPU HW error.
0x0080 (sdramError)
SDRAM test failed indicating CPU HW error.
0x0100 (xilinxInitError)
CPU HW error caused by the Xilinx.
0x1000 (pldSRAMMagicStrFillFailed)
If the IED started with power supply off/on
switching, it tries to write a control data string in
the SDRAM. If this operation fails, the error
message appears indicating the CPU HW
error.
0x2000 (pldSelfCheckFailed)
Self-check function detected a failure.
Suspected CPU HW error.