January 12, 2009
DPV1 Class 1 Read and Write
Failure Error
source
0 No
error
DPV1 Class 1 Alarm Request
Failure Description
0 TASK_F_OK
No error
115 DPS_ERR_DIAG_TOO_LONG
Status data exceeds the length of the diagnostic buffer.
116 DPS_ERR_NO_FREE_DIAG_BUFFER
No diagnostic buffer available at the moment
This Error will be temporary.
119 DPS_ERR_ALRM_DPV1_C1_DEACTIVATED
DPV1 class 1 services are disabled
120 DPS_ERR_ALRM_OVERFLOW
Maximum number of active alarms exceeded
121 DPS_ERR_ALRM_DISABLED
Alarm is disabled
123 DPS_ERR_ALRM_ILLEG_LEN
User specific alarm data of illegal length
125 DPS_ERR_ALRM_ILLEG_SEQU
Sequence number out of range or already in use
152 TASK_F_MESSAGECOMMAND
Unknown command in "Command" Field
165 TASK_F_DATA_CNT
Mismatch between length in "length" field and length of message data
200 TASK_F_NOT_INITIALIZED
Task not initialized
5.5
Constructing a Bus Cable for PROFIBUS DP
The bus cable for connecting PROFIBUS DP devices must be constructed by the
user. A special PROFIBUS cable (twisted pair) is required here. This standard
cable is available from various manufacturers and is a Belden part number
3079A.
If you plan to construct your own bus cable, the following part numbers are
provided for your convenience.
PROFIBUS connector: Siemens part number 6ES7972-0BA40-0XA0
PROFIBUS cable: Belden part number 3079A.
To construct the cable, proceed as follows:
1
Cut the cable to the required length.