5.4 Communication
5.4.1 IO Communication and IO Memory Map
Contained in the following sections are the I/O memory mappings for the PS69-
DPS interface. The I/O area will be used for communication of status and
command information as well as cyclic I/O data.
IO Array Overview
We use the term "Byte" for 8-bit values; we use the term "Word" for 16-bit values.
Module Input Array
Below is a summary of the register layout of the input area of the PROFIBUS
Slave module. The offset values are defined as byte.
Offset Register
Type
Name
0
Device Status Register
Status Bits
1 Reserved
Reserved
2 Reserved
Reserved
3 Reserved
Reserved
4
Firmware Revision
Minor Version
5
Firmware Revision
Major Version
6-7 Reserved
Reserved
8-9
Slave Status Information
ExtStaSelect
10-11
Slave Status Information
ExtStaLen
12-13
Slave Status Information
Baudrate
14
Slave Status Information
Busaddress
15
Slave Status Information
UserFlags
16-17
Slave Status Information
Ident
18-19
Slave Status Information
TaskState
20-21
Slave Status Information
InputDataLen
22-23
Slave Status Information
OutputDataLen
24-25
Slave Status Information
ErrorCount
26
Slave Status Information
LastError
27
Slave Status Information
Reserved
28-29
Slave Status Information
WatchdogTime
30-31
Slave Status Information
IrqCounter
32-37
Slave Status Information
Dpv1StatusRegister
38-39
Slave Status Information
Reserved
40-135
Slave Status Information
ExtStatusInfo[96]
136-379
PROFIBUS Output Area
PBOutputData