PS69-DPS
♦
CompactLogix or MicroLogix Platform
Reference
Profibus DP Slave Communication Module
Page 76 of 94
ProSoft Technology, Inc.
January 12, 2009
Parameter Data
Type
Value Description
Command
SINT
18
Command for Service
DPV1 Class 1 Alarm Request
Reserved4 SINT 0
Reserved
Reserved5 INT
0
Reserved
SlotNumber
INT
0...254
Alarm Slot Number
SequenceNumber SINT
0...31
Alarm
Sequence
Number
DataCnt SINT 0...28
(x)
Number of User Specific Alarm Data
AlarmType SINT 1-6,
32-126
Alarm Type:Diag,-Process,-Pull,-Plug,-Status,-Update,
Manufacturer specific
Specifier SINT 0...7 Alarm
Specifier
Bit 0...1: Alarm Specifier
Bit 2: Add Ack bit
Data[0..x]
SINT[28]
0…255
User Specific Alarm Data.
DPS_B_ACYC_C1_ALARM _CONFIRM
Parameter Data
Type
Value Meaning
Reserved1 INT
0
Reserved
Reserved2 INT
0
Reserved
Answer
SINT
18
Answer DPS_B_ACYC_C1_ALARM
Failure
SINT
e
Error, status (see following section)
Reserved3 INT
0
Reserved
Reserved4 INT
0
Reserved
SlotNumber
INT
0...254
Alarm Slot Number, Reply from request
SequenceNumber
SINT
0...31
Alarm Sequence Number, Reply from request
DataCnt SINT 0
not
used
DataType SINT 1-6,
32-126
Alarm Type, Reply from request
Specifier
SINT
0..7
Alarm Specifier, Reply from request
CIP MSG Parameterization
Parameter Value
Remarks
Message Type
CIP Generic
Service Type
Custom
Service Code
64 hex
Service Code "Bridge Message"
Class
65 hex
CIP Object "CIP_MSG_BRIDGE""
Instance 1
Attribute 0
Source Element
Dpv1AlarmReq
Reference to a Tag of type
DPS_DPV1C1_ALARM_REQUEST
Destination
Dpv1AlarmCnf
Reference to a Tag of type
DPS_DPV1C1_ALARM_CONFIRM
Source Length
16 + n
n = Number user specific Alarm Data (0 .. 28)