PS69-DPM ♦ CompactLogix or MicroLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 90 of 130
ProSoft Technology, Inc.
October 1, 2014
MSAL1M_Alarm_Res
Failure
Significance
Error source Help
86 hex = REJ_INT
The alarm handler is not
initialized
DEVICE
No DPV1 capable device configured within the
card
87 hex = REJ_SRT
The alarm handler is currently
stopped
DEVICE
No DPV1 capable slave device is in process
data exchange with the DEVICE. Check if
network is running
88 hex = REJ_ENA
The alarm that shall be
acknowledged is not enabled in
slave parameter data
HOST
Enable the corresponding alarm in slave
configuration data set
89 hex = REJ_NPD The alarm that shall be
acknowledge is not pending on
a MSAL1_Alarm_Res
HOST
Check the parameter Alarm_Type and
Seq_Nr. Both must be equal to the
MSAL1_Alarm_ind parameter
9a hex = REJ_COM Unknown msg.b command
HOST
Correct the requested msg.b parameter of
message