Code
Indication
Source
Corrective Action
56
Non Existing Slave Parameters
Configuration
Execute download of configuration
database again.
57
Faulty Parameter Value in a Slave
Parameters
Configuration
Check GSD file for possible incorrect slave
parameterization values.
58
Duplicate Slave Address
Configuration
Check configured slave addresses in
project.
59
Projected Send Process Data Offset
Address of a Slave is Outside the
Limits of 0 to 255
Configuration
Check slave configuration in active project.
60
Projected Receive Process Data
Offset Address of a Slave is Outside
the Limits of 0 to 255
Configuration
Check slave configuration in active project.
61
Data-Areas of Slaves are
Overlapping in the Send Process
Data
Configuration
Check slave configuration in active project.
62
Data-Areas of Slaves are
Overlapping in the Receive Process
Data
Configuration
Check slave configuration in active project.
63
Unknown Process Data Handshake Master
Problem with master’s startup parameters.
64
Free RAM Exceeded
Master
Master has a hardware issue.
65
Faulty Slave Parameter Dataset
Configuration
Check GSD file for possible incorrect slave
parameterization datasets.
202
No Memory Segment Available
Master
Master has a hardware issue.
212
Faulty Reading of a Database
Configuration
Execute download of configuration
database again.
213
Structure Used by the Operating
System is Faulty
Master
Master has a hardware issue.
220
Software Watchdog Error
Host
Firmware watchdog has an error.
221
No Data Acknowledge in Process
Data Handshake
Host
Firmware is having trouble with Host
acknowledgement.
222
Master in Auto_Clear
Slave Device
The auto_clear mode was activated,
because one slave is missing during
runtime.
225
No Further Segments
Master
Contact hotline
ERROR_EVENT Codes for an Err_Rem_ Adr of not equal to 255
Code
Indication
Source
Corrective Action
2
Slave Station Reports Data
Overflow
Master Telegram
Check length of configured slave parameter
or configuration data.
3
Request Function of Master is not
Supported in the Slave
Master Telegram
Check if slave is PROFIBUS-DP norm
compatible.
9
No Answer, Although the Slave
must Respond with Data
Slave
Check configuration data of the slave and
compare it with the physical I/O data
length.
17
No Response from the Slave
Slave
Check bus cable, and bus address of slave.