ProLinx DNPS
♦
ProLinx Gateway
Start Here
DNP 3.0 Slave
User Manual
Page 22 of 86
ProSoft Technology, Inc.
December 1, 2009
Unsol Resp Delay
0 to 65535 milliseconds
Maximum number of 1 millisecond intervals to wait after an event occurs before
sending an unsolicited response message. If set to 0, only use minimum number
of events.
Uresp Master Address
0 to 65534
DNP destination address where unsolicited response messages are sent.
AI Events with time
Y or N
This parameter determines if the analog input events generated by the module
will include the date and time of the event. If the parameter is set to N, the default
is set to no time data. If the parameter is set to Y, the default object will include
the time of the event.
Time Sync Before Events
Y or N
This parameter determines if events are to be generated by the module before
the time synchronization from the master unit. If the parameter is set to N, no
events will be generated until the module’s time has been synchronized. If the
parameter is set to Y, events will always be generated.
1.4.2 [DNP Slave Binary Inputs]
This area is to override the class (2) binary input database points.