Configure the Adapter for Master/Slave Communication
3170-PDP
♦
FLEX Platform
FLEX I/O™ PROFIBUS Adapter
ProSoft Technology, Inc.
Page 63 of 152
August 23, 2007
User Parameter Message, Full Format (Length 43 bytes)
Name Value
Description
Octet 32 to 33:
0000h
4 safe state data words – safe state value for output point 1
output point 2
output point 3
output point 4
Octet 34 to 35:
0000h
Octet 36 to 37:
0000h
Octet 38 to 39:
0000h
Octet 40 to 41:
0FFFFh
Slot 5 empty
Octet 42:
00h
Slot 5 all sizes zero
Octet 43 to 44:
0FFFFh
Slot 6 empty
Octet 45:
00h
Slot 6 all sizes zero
Octet 46 to 47:
0FFFFh
Slot 7 empty
Octet 48:
00h
Slot 7 all sizes zero
Octet 49 to 50:
0FFFFh
Slot 8 Empty
Octet 51:
00h
Slot 8 all sizes zero
Octet 52 to 244
00h
Not Used
After you enter all octet values, click
In the 3170-PDP Device Parameters screen, click
You see the Modules Information screen:
Select each of the possible modules in the Possible Modules column, then click
on
. Repeat this for the four FLEX I/O modules in the example. Also
add 3170-PDP Status (counts as one module) and three Flex I/O empty slot
modules. All eight slots must be accounted for.
Notice as you add each module, the
Module Configuration
status appears:
If you want to edit the configuration of a module, select the module and click on