How Communication Takes Place and I/O Image Table Mapping
3170-PDP
♦
FLEX Platform
FLEX I/O™ PROFIBUS Adapter
ProSoft Technology, Inc.
Page 29 of 152
August 23, 2007
1794-IE8 Range Selection Bits
Channel
No.
Channel
0
Channel
1
Channel
2
Channel
3
Channel
4
Channel
5
Channel
6
Channel
7
F0 C0 F1 C1 F2 C2 F3 C3 F4 C4 F5 C5 F6 C6 F7 C7
Decimal
Bit 00 08 01 09 02 10 03 11 04 12 05 13 06 14 07 15
0 to 10V dc/0
to 20mA
1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0
4
to
20mA 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
–10 to +10V
dc
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Do
Not
Use1
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
C = Configure select bit
F = Full range bit
1 Do not use this configuration. Individual channels revert to 4 to 20mA if bit selection is all zeroes.
1794-IE8 Word/Bit Descriptions
Word Decimal
Bit
Definition
Read Word 1
Bits 00 to 14
Channel 0 analog data – 12-bit left justified two's
complement number; unused lower bits are zero; 4 to 20mA
uses all 16 bits.
Bits 15
Channel 0 analog data sign bit.
Read Word 2
Bits 00 to 14
Channel 1 analog data – 12-bit left justified two's
complement number; unused lower bits are zero; 4 to 20mA
uses all 16 bits.
Bits 15
Channel 1 analog data sign bit.
Read Word 3
Bits 00 to 14
Channel 2 analog data – 12-bit left justified two's
complement number; unused lower bits are zero; 4 to 20mA
uses all 16 bits.
Bits 15
Channel 2 analog data sign bit.
Read Word 4
Bits 00 to 14
Channel 3 analog data – 12-bit left justified two's
complement number; unused lower bits are zero; 4 to 20mA
uses all 16 bits.
Bits 15
Channel 3 analog data sign bit.
Read Word 5
Bits 00 to 14
Channel 4 analog data – 12-bit left justified two's
complement number; unused lower bits are zero; 4 to 20mA
uses all 16 bits.
Bits 15
Channel 4 analog data sign bit.
Read Word 6
Bits 00 to 14
Channel 5 analog data – 12-bit left justified two's
complement number; unused lower bits are zero; 4 to 20mA
uses all 16 bits.
Bits 15
Channel 5 analog data sign bit.
Read Word 7
Bits 00 to 14
Channel 6 analog data – 12-bit left justified two's
complement number; unused lower bits are zero; 4 to 20mA
uses all 16 bits.
Bits 15
Channel 6 analog data sign bit.