3170-PDP
♦
FLEX Platform
Configure the Adapter for Master/Slave Communication
FLEX I/O™ PROFIBUS Adapter
Page 60 of 152
ProSoft Technology, Inc.
August 23, 2007
Check Configuration Example
Check Configuration Message when used with Send Parameter Full Format (Length 10
bytes)
Name Identifier
Byte
Description
Octet 1:
50h
Status Word (input – 1 word)
Octet 2:
60h
Output Status Word (output – 1 word)
Octet 3:
50h
Slot 1, input module 1 word
Octet 4:
00h
Slot 1, output module empty
Octet 5:
00h
Slot 2, input module empty
Octet 6:
60h
Slot 2, output module 1 word
Octet 7:
58h
Slot 3, input module 9 words
Octet 8:
00h
Slot 3, output module empty
Octet 9:
50h
Slot 4, input module 1 word
Octet 10:
63h
Slot 4, output module 4 words
I/O sizes configured: 24 input bytes, 12 output bytes
The read configuration message response returns the current configuration data.
At power up, the configuration is the maximum read and write sizes supported by
each FLEX I/O module.
5.3
Read Configuration Response Data
A valid check configuration message updates the internal configuration. The
updated internal configuration is then returned in the message response.
Power Up Configuration Example
Read Configuration Message response at Power Up (Length 10 bytes)
Name Identifier
Byte
Description
Octet 1:
50h
Status Word (input - 1 word)
Octet 2:
60h
Output Status Word (output - 1 word)
Octet 3:
51h
Slot 1, input module 2 words
Octet 4:
60h
Slot 1, output module 1 word
Octet 5:
50h
Slot 2, input module 1 word
Octet 6:
61h
Slot 2, output module 2 words
Octet 7:
58h
Slot 3, input module 9 words
Octet 8:
65h
Slot 3, output module 6 word
Octet 9:
50h
Slot 4, input module 1 word
Octet 10:
60h
Slot 4, output module 14 words
Refer to the configuration example to understand how and where to enter this
data. If you are using the Rockwell Automation PROFIBUS Manager
configuration software, follow this example to understand how to access and
enter data. This example is a User Parameter Message, Full Format.