![ProSoft Technology inRAx 3170-PDP Скачать руководство пользователя страница 57](http://html1.mh-extra.com/html/prosoft-technology/inrax-3170-pdp/inrax-3170-pdp_user-manual_1618906057.webp)
Configure the Adapter for Master/Slave Communication
3170-PDP
♦
FLEX Platform
FLEX I/O™ PROFIBUS Adapter
ProSoft Technology, Inc.
Page 57 of 152
August 23, 2007
User Parameter Message, Full Format
Name Value
Description
Octet 9:
OBh
Full Format, Use Safestate
Octet 10 to 11:
0281h
Slot 1 Module Key 1794-IB16 16-point discrete input module
Octet 12 to 13
10h
Slot 1 config size 1 word, safe state size 0 words
Octet 13 to 14:
0000h
1 config word, input delay times
Octet 15 to 16:
0191h
Slot 2 Module Key 1794-OB16 16-point discrete output module
Octet 17:
01h
Slot 2 config size 0 words, safe state size 1 word
Octet 18 to 19:
0000h
1 safe state data word, safe state value for output points
Octet 20 to 21:
1920h
Slot 3 Module Key 1794-IE8 8-point analog input module
Octet 22:
10h
Slot 3 config size 1 word, safe state size 0 words
Octet 23 to 24:
0000h
1 config word, channel selection
Octet 25 to 26:
5121h
Slot 4 Module Key 1794-OE4 4-point analog output module
Octet 27:
24h
Slot 4 config size 2 words, safe state size 4 words
Octet 28 to 29:
0000h
4 safe state data words – safe state value for output point 1
output point 2
output point 3
output point 4
Octet 30 to 31:
0000h
Octet 32 to 33:
0000h
Octet 34 to 35:
0000h
Octet 36 to 37:
0000h
2 config words – channel selection and
output enable
Octet 38 to 39:
0000h
Octet 40 to 41:
0FFFFh
Slot 5 empty
Octet 42:
00h
Slot 5 all sizes zero
Octet 43 to 44:
0FFFFh
Slot 6 empty
Octet 45:
00h
Slot 6 all sizes zero
Octet 46 to 47:
0FFFFh
Slot 7 empty
Octet 48:
00h
Slot 7 all sizes zero
Octet 49 to 50:
0FFFFh
Slot 8 Empty
Octet 51:
00h
Slot 8 all sizes zero
Octet 52 to 244 00h
Not Used
Refer to the configuration example to understand how and where to enter this
data. On a PROFIBUS DP network, the I/O data exchanged between the
PROFIBUS DP master and a DP slave is encapsulated into
logical modules.
The total I/O data exchanged between a PROFIBUS DP master and a DP slave
device comprises a set of logical modules which is defined in the check
configuration data.