Send Parameter Data Flags Byte
Bit Position Name
Description
2 to 3
Fault
Action
00 = Reset to zero
01 = Hold Last State
10 = Use Safe State
11 = Reserved
4
Format
Selection
0 = Reset inputs to zero
1 = Hold Last Value
5 to 7
Reserved Reserved bits must be zero
If the send parameter data is received with no user parameter data, the flags
byte is set to zero which selects:
auto
configure
reset outputs to zero on fault
reset inputs to zero on fault
The reserved bits must be set to zero to prevent undesired firmware update
behavior. This is the default behavior of the module as defined in the
PSFT0882.GSD file.
The descriptions in this chapter use the following example FLEX I/O
configuration to explain the information required for each of these functions:
5.2.2 Auto Configure Format
The Auto Configure format allows you to change modules without affecting the
User Parameter or Check Configuration data. This format provides no keying
from the master on the I/O modules installed in the FLEX I/O system. The
installed module at power-up is taken as the key.
If you change a module while it is being controlled by a master, a minor
recoverable fault will occur. To recover from this fault, you must replace the
module with an identical module type.