Identity code
specification
Phases, protec‐
tion
Rated voltage
Mains frequency
Rated output
Remarks
L1
3-phase, II 2G Ex
h IIC Gb T3 X
220-240 V /
380-420 V
50 Hz
0.18 kW
L2
3-phase, II 2G Ex
h IIC Gb T4 X
220-240 V /
380-420 V
50 Hz
0.18 kW
With PTC, speed
control range 1:5
P1
3-phase, II 2G Ex
h IIC Gb T3 X
250-280 V /
440-480 V
60 Hz
0.18 kW
P2
3-phase, II 2G Ex
h IIC Gb T4 X
250-280 V /
440-480 V
60 Hz
0.21 kW
With PTC, speed
control range 1:5
Motor data sheets, special motors, special motor
flanges, external fan, temperature monitoring
–
For further information on the motor with identity
code specification "S", refer to our website
www.prominent.com. Motor data sheets can be
requested for all other motors.
–
With motors other than those with identity code
specifications "S", "M" or "N": Pay special attention
to the operating instructions for the motors.
–
Special motors or special motor flanges are avail‐
able on request.
15.8 Stroke actuator
Voltage
Mains frequency
Output
85 ... 265 V AC
50/60 Hz
11.7 W
15.9 Stroke control drive
Voltage
Mains frequency
Output
85 ... 265 V AC
50/60 Hz
6.5 W
15.10 Diaphragm rupture sensor
Install the sensor in accordance with the chapter "Installation, electrical".
Tab. 7: Contact loading, max.
with voltage
Maximum current
30 V DC
1 A
The diaphragm rupture sensor is an N/C.
n
For safety reasons we recommend connection to protective low
voltage, e.g. in accordance with EN 60335-1 (SELV).
n
The cable can be connected as required.
Install the sensor in accordance with the chapter "Installation, electrical".
Refer to its documentation.
Sensor name: NJ1.5-8GM-N.
a) Contact (standard with identity code
specification "Displacement mechanism“:
A)
a) Namur sensor (for identity code specifi‐
cation "Displacement mechanism“: A)
Technical data