Terminal
Selection
Remark
minimum
switching on
time
0.0 ... 1250.0 seconds
The switching on time is limited to 20 % of the cycle time
The cycle times are to be taken into consideration when actuating solenoid valves (PWM = pulse width
modulation).
7.1.1 Solenoid valve relay
Cycle
min. time
Solenoid
valve
off
on
t
t
on
off
on
t
t
on
Cycle
Actuating
variable: 50 %
t
on
Cycle
= 0.50
Actuating
variable: 80 %
t
on
Cycle
= 0.80
A0025_GB
Fig. 13: Solenoid valves
The switching times of the relay (solenoid valve) depend on the
actuating variable and the "min. time" (smallest permissible
switching time of the connected device). The actuating variable
determines the ratio t
on
/cycle and thus also the switching times.
The "min. time" affects the switching times in two situations:
off
on
t
off
on
t
Cycle
Cycle
Cycle
Cycle
Cycle
Cycle
min. time
min. time
theoretical
actual
A0026_GB
Fig. 14: theoretical switching time < min. time
The DULCOMARIN
®
3 does not switch on for a certain number of
cycles until the sum of the theoretical switching times exceeds the
"min. time". Then the DULCOMARIN
®
3 switches for the duration
of this total time.
first theoretical switching time < min.
time
Configuring the P-module (DXMaP) (power module)
24