Wiring Diagram
Wire sizing data is provided in the Wire Sizing Data table to assist in the selection of
the proper wire size for ProMation P1.A series actuators using various wire sizes over
distance. Please make sure to reference the correct voltage and do not exceed the
indicated length of the wire run for each model.
Proportional Control
MAX distance between
Actuator and Supply (feet)
Actuator/
Voltage
P1.A
12VAC/DC
P1.A
24VAC/DC
1.5A
0.9A
18
55
184
16
87
289
14
140
466
Wire
Gage
Amps
Wire Sizing Chart
12/24VAC or 12/24VDC
AC Hot or DC+
AC Neu or DC-
BLK
WHT
The default settings in the controller are as follows:
1. Input/Output Signal:
4-20mA only
2. Signal Response:
Direct Acting (max signal = CCW)
3. Loss of Signal:
Fail in Position
4. Sensitivity Setting
3: Approximately 30 steps for 90°