Promation Engineering P1.A Series Скачать руководство пользователя страница 13

FM14_P1A

 L

V VN4 V

er J 101614

Page 11 of 14 P1.A LV AdVanced Proportional Series

Commissioning

This procedure will assume that the actuator is installed correctly both mechanically and electrically with correct power at 
terminals marked 4 & 5 and control signal at terminals marked 6 & 7
1.  Apply the correct supply power to the actuator. (DIP 5 ON)

• 

NOTE -  Power is measured at terminals marked 4 & 5 on the actuator.

• 

The POWER (Yellow) LED will illuminate whenever power is on.

1.A  NORMAL OPERATION

I. 

The Diagnostics (Blue) LED will flash once every second if the control signal is correct (between 4 and 20mA)

II.  Proceed to step 2.

1.B  FAULT STATUS

I. 

The Diagnostics (Blue) LED will show a FAULT by flashing 3 times followed by 1 sec pause. The actuator will 

not operate correctly while in a FAULT status.

1a. The Diagnostics (Blue) LED shows FAULT if the 

Control Wires are not in place or out of range

.

• 

If the Control Wires are connected at terminals marked 6 & 7 and there is still a FAULT, generate a 

20mA control signal across terminals marked 6 and 7 (from the PLC or utilize a signal generator)

1b. The Diagnostics (Blue) LED shows FAULT AND the ORANGE LED is illuminated if the 

Control Wires are 

reversed

 at terminals marked 6 & 7.

NOTE -  The control signal can be measured with a digital multimeter set for mA connected in series with 

terminal 7.

II.  When FAULT is cleared proceed to step 2.

2.  Test Full CW and CCW Positions for 

Direct Acting Mode

 (DIP 3 set to OFF) 

2.A  Generate a 20mA control signal at the PLC or signal generator. 

I.  The actuator OUTPUT shaft will drive to the 

full CCW

 position while the INDICATOR/cam shaft rotates to the 

full CW position (as viewed from ABOVE the actuator). 

II.  If this is NOT the correct stop position, refer to Adjusting the actuator CCW position instructions for CAM 1 on 

Page 7 in this document.

2.B  Generate a 4mA control signal at the PLC or signal generator. 

I.  The actuator OUTPUT shaft will drive to the 

full CW

 position while the INDICATOR/cam shaft rotates to the 

full CCW position (as viewed from ABOVE the actuator).  

II.  If this is NOT the correct stop position, refer to Adjusting the actuator CW position instructions for CAM 2 on 

Page 7 in this document.

3.  Test Full CW and CCW Positions for 

Reverse Acting Mode

 (DIP 3 set to ON) 

3.A  Generate a 20mA control signal at the PLC or signal generator. 

I.  The actuator OUTPUT shaft will drive to the 

full CW

 position while the INDICATOR/cam shaft rotates to the 

full CCW position (as viewed from ABOVE the actuator).  

II.  If this is NOT the correct stop position, refer to Adjusting the actuator CW position instructions for CAM 2 on 

Page 7 in this document.

3.B  Generate a 4mA control signal at the PLC or signal generator. 

I.  The actuator OUTPUT shaft will drive to the 

full CCW

 position while the INDICATOR/cam shaft rotates to the 

full CW position (as viewed from ABOVE the actuator). 

II.  If this is NOT the correct stop position, refer to Adjusting the actuator CCW position instructions for CAM 1 on 

Page 7 in this document.

NOTE-   The feedback signal generator shows the 4-20mA position output at terminals marked 11 (-) & 12 (+). 

IF THE END OF TRAVEL CAMS ARE ADJUSTED, THEN THE ACTUATOR MUST BE RECALIBRATED. REFER TO 
THE AUTOCALIBRATION PROCEDURE ON PAGE 12.

Содержание P1.A Series

Страница 1: ...Installation Operation Manual This IOM is for the following ProMation Engineering Products P1 A 12VN4 AC P1 A 12VN4 DC P1 A 24VN4 AC P1 A 24VN4 DC...

Страница 2: ...This page intentionally left blank...

Страница 3: ...ts 2 Product Specifications 3 Shipping and Handling 3 Product Mounting and Setup 3 Installation Notes 4 Wiring Diagram 5 Layout of Controller 6 Check End of Travel Settings 6 Check End of Travel Setti...

Страница 4: ...e Duty Cycle is directly related to heat excessively repositioning an actuator typically results in motor overheating which can cause permanent damage and or reduced service life Duty cycle can be cal...

Страница 5: ...y CCW positions BEFORE applying power to the unit Warning DO NOT operate manual override when power is present Geartrain damage and personal injury may occur Do not use powered tools to turn the manua...

Страница 6: ...d do not exceed the indicated length of the wire run for each model Proportional Control MAX distance between Actuator and Supply feet Actuator Voltage P1 A 12VAC DC P1 A 24VAC DC 1 5A 0 9A 18 55 184...

Страница 7: ...D Running CCW Indicator Green LED Proportional Control DIP Switch Setting Default Functions DIP 1 Off Run Mode DIP 1 On Calibration CAL Mode DIP 2 Off Direct Acting Mode DIP 2 On Reverse Acting Mode D...

Страница 8: ...d of Travel cams have set the rotation for 90 travel Reset to 90 travel and AutoCalibrate Power On DIP 5 on No Motor Movement Red or Green Motor Direction LEDs Flash Low Power Incoming Power too low T...

Страница 9: ...tate the hex key to the LEFT 10 15 degrees to reset the switch roller arm Then snug the set screw up against the camshaft CW until slight pressure is felt Then SLOWLY rotate the hex key to the RIGHT u...

Страница 10: ...the CW auxiliary switch adjustment Drive the actuator to its CW position Then use a 2 5mm hex key to free up the cam set screw Once it is free rotate the hex key to the LEFT 10 15 degrees to reset th...

Страница 11: ...Pushed square dimension to three decimal places KHL REV A B C D E F Drive Coupling Fabrication Data 17 00 13 00 mm 0 669 0 005 0 000 in 17 00 13 00 mm 0 669 0 005 0 000 in 17 00 mm 0 669 in 127 mm 5 0...

Страница 12: ...is provided in the table belowtoshowthechange of statepointsduring the rotation of the actuator from CCW to CW and back again The red bar shows when that terminal makes with its respective common Swi...

Страница 13: ...ator I The actuator OUTPUT shaft will drive to the full CCW position while the INDICATOR cam shaft rotates to the full CW position as viewed from ABOVE the actuator II If this is NOT the correct stop...

Страница 14: ...ves actuator to fully CW 7 The CW End of Travel switch opens and motor stops 8 The Green LED goes on and motor drives to fully CCW 9 The CCW End of Travel switch opens and motor stops 10 Red LED goes...

Страница 15: ...otor drives to Fully CCW 4 The CCW End of Travel switch opens and motor stops 5 Red LED goes on and actuator drives to Fully CLOSED 6 The controller performs an internal Calibration of the Feedback Bl...

Страница 16: ...n Pass Feedback Calibration Fail 20Hz Blink 30 seconds 1Hz Blink Inde nitely 20Hz Blink 3 seconds NO YES Did the Blue LED flash at 20Hz for three 3 seconds DIAG DIAG DIAG Check that Wire Jumper connec...

Страница 17: ...ProMation Engineering Inc 16138 Flight Path Drive Brooksville FL 34604 Phone 352 544 8436 Fax 352 544 8439 www promationei com...

Страница 18: ...igital form We regularly host customized educational webinars for our customers RapidQuote Most quotes and estimates are generated within hours of the request ProMation Engineering Services ProMation...

Отзывы: