background image

43 

 

4. Trouble Shooting

 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom 

Possible cause 

Remedy 

No  indication  and  alarm  in  the  front 

display panel even though the mains is 

normal.   

The  AC  input  power  is  not 

connected well. 

Check  if  input  cable  firmly 

connected to the mains.   

The warning code 0B. 

EPO  function  is  activated.  At 

this time, the EPO switch is in 

“OFF”  status  or  the  jumper  is 

open. 

Set  the  circuit  in  closed 

position  to  disable  the  EPO 

function.   

The warning code 01. 

The  external  or  internal 

battery 

is 

incorrectly 

connected. 

Check  if  all  batteries  are 

connected well. 

The warning code 09. 

UPS is overload.   

Remove excess loads from UPS 

output. 

UPS  is  overloaded.  Devices 

connected  to  the  UPS  are  fed 

directly  by  the  electrical 
network via the Bypass. 

Remove excess loads from UPS 

output. 

After  repetitive  overloads,  the 

UPS  is  locked  in  the  Bypass 

mode.  Connected  devices  are 

fed directly by the mains. 

Remove excess loads from UPS 

output  first.  Then  shut  down 

the UPS and restart it. 

Fault code is shown as 43.   

UPS  is  overload  too  long  and 

becomes fault. Then UPS shut 

down automatically. 

Remove excess loads from UPS 

output and restart it. 

Fault code is shown as 14,

 

15,

 

16,

 

17,

 

18 or 19,   

The 

UPS 

shut 

down 

automatically  because  short 

circuit  occurs  on  the  UPS 

output. 

Check  output  wiring  and  if 

connected devices are in short 

circuit status. 

Other  fault  codes  are  shown  on  LCD 

display and alarm beeps continuously. 

A  UPS  internal  fault  has 

occurred.   

Contact your dealer 

Battery  backup  time  is  shorter  than 

nominal value. 

Batteries are not fully charged. 

Charge  the  batteries  for  at 

least  7  hours  and  then  check 

capacity.  If  the  problem  still 

persists, consult your dealer.   

Batteries defect 

Contact your dealer to replace 

the battery. 

The warning code 0A. 

Fan  is  locked  or  not  working. 

Or the UPS temperature is too 

high. 

Check fans and notify dealer.   

The warning code 02. 

The  input  neutral  wire  is 

disconnected. 

Check  and  correct  the  input 

neutral  connection.  If  the 

connection  is  ok  and  the 

warning  is  still  displaying, 

please enter LCD setting menu 

ADVANCE

  User

  Electric. 

Then, select “CHE” and restart 

the UPS. 

Содержание MASTER II Series

Страница 1: ...ONLINE UPS User Manual PRO 83300QRS QRL 3P 3P or 3P 1P or 1P 1P TOWER PRO83300 QRS QRL 10KVA 20KVA Version 1 00 English...

Страница 2: ...ND INSPECTION 4 2 2 WIRING TERMINAL VIEW 5 2 3 SINGLE UPS INSTALLATION 6 2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 8 3 OPERATIONS 9 3 1 BUTTON OPERATION 9 3 2 SCREEN DESCRIP...

Страница 3: ...on the UPS housing 1 3 Installation Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output terminal Place cables in such a way that no one can...

Страница 4: ...r nitrous oxide Connect grounding terminal of UPS to a grounding electrode conductor In accordance with safety standard EN IEC 62040 1 installation has to be provided with a Backfeed Protection system...

Страница 5: ...that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 6 Standards Safety IEC EN 62040 1 EMI Conducted Emission...

Страница 6: ...tents The shipping package should contain One UPS One user manual One monitoring software CD One RS 232 cable option One USB cable One parallel cable only available for parallel model One shared curre...

Страница 7: ...agram 1 Front panel Diagram 2 HV10KL LV5KL Rear Panel Diagram 3 HV15KL HV20KL LV7 5KL LV10KL 1 Power switch 2 External maintenance bypass switch port 3 USB communication port 4 Emergency power off fun...

Страница 8: ...7 5KL 12 12 10 8 8 LV 10K HV 20K 10 10 6 8 6 NOTE 1 The cable for HV 10KL and LV 5KL should be able to withstand over 20A current It is recommended to use AWG 14 or thicker wire for Phase and AWG10 o...

Страница 9: ...eaker in OFF position and then install the battery pack Pay special attention to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery in a chain make sur...

Страница 10: ...o an output breaker 3 Connect all output breakers to a major breaker This major output breaker will then connect directly to the loads 4 Either common battery packs or independent battery packs for ea...

Страница 11: ...Screen Description After initialization the LCD will display main screen There are five sub menus Control measure setting information and data log Touch any sub menu icon to enter into the sub screen...

Страница 12: ...few seconds as shown below After initialization the main screen will display as shown below After touching the icon it will show five icons in center to represent five sub menus Control measure setti...

Страница 13: ...turn LCD CHANGE BATT TEST Confirm YES DO LCD CHANGE Enter or return EXIT PARALLEL Confirm YES DO EXIT PARALLEL Single machine cannot do this Screen 1 0 Control and its sub menus On Off UPS It will sho...

Страница 14: ...t will show Stop battery test if the UPS is in test Battery Test Cancel Battery Test Mute All It will show Mute all if the audio is active Touch Yes to activate mute If Mute all is active it will show...

Страница 15: ...o CONTROL screen Touch HOME to return to main screen Tower Display Rack Display Exit Parallel If the UPS is set as parallel mode you can touch this icon to stop parallel mode Touch Yes to stop paralle...

Страница 16: ...he real time value of L1 L2 and L3 phase voltage L1L2 L2L3 L3L1 voltage and input frequency BYPASS VOLT The real time value of L1 L2 and L3 bypass voltage L1L2 L2L3 L3L1 voltage and frequency Measure...

Страница 17: ...1 L2 and L3 input power watt in percentage Measure screen page 4 INPUT VA L1 L2 and L3 input power in VA INPUT VA L1 L2 and L3 input power VA in percentage Measure screen page 5 OUTPUT W L1 L2 and L3...

Страница 18: ...n VA OUTPUT VA L1 L2 and L3 output power VA in percentage Measure screen page 7 INPUT CURR L1 L2 L3 input current in Amp INPUT PF L1 L2 L3 input power factor Measure screen page 8 OUTPUT CURR L1 L2 L3...

Страница 19: ...related information 3 2 4 Setting screen This sub menu is used to set the parameters of UPS Touch the icon to enter setting menu page There are 2 options General and Advanced Touch the icon to return...

Страница 20: ...DVANCE It s required to enter password to access to the ADVANCED setting There are two types of authority User and Maintainer HOME SETTING GENERAL SELFTEST BATT SYS PARA INSTALL INITIAL VOL CALI CURR...

Страница 21: ...here are three options English Simplified Chinese and Traditional Chinese English is default setting Input Source Select the input source There are two options Line utility and generator Line is defau...

Страница 22: ...ll NOT alarm when warning occurs Mode Mute Disable When selected the UPS will alarm when UPS related status changes Enable When selected the UPS will NOT alarm when UPS related status changes Volume S...

Страница 23: ...nt voltage and constant frequency function Enable CVCF function is enabled The output frequency will be fixed at 50Hz or 60Hz according to setting of OP Freq The input frequency could be from 40Hz to...

Страница 24: ...is 130V 146V when UPS is LV system Bypass Frequency Range Set the bypass frequency range The acceptable bypass frequency range from 46Hz to 54Hz when UPS is 50Hz system and from 56Hz to 64Hz when UPS...

Страница 25: ...ing Battery age if battery age is beyond the setting month then the UPS will alarm for reminding The factory default setting is 24 months Battery AH Setting battery capacity OTHERS OTHERS setting page...

Страница 26: ...is setting menu is only for qualified technician Otherwise mis operation will cause UPS damage There are 9 sub menus under Advance Maintainer setting SYS PARAMETER INSTALL INITIAL VOL CALI CURR CALI S...

Страница 27: ...0 16 is default setting Charger VOL The setting point of battery float voltage 13 6V is default setting INSTALL INSTALL Page System Install Date Set the date of UPS installation Battery Install Date S...

Страница 28: ...AGE CALIBRATE Page3 Line VOL Line voltage calibration Click value columns and it will pop up Then each click is 0 1 no matter it s pressing up or down key Press up key to increase 0 1 and press down k...

Страница 29: ...key Press up key to increase 0 1 and press down key to decrease 0 1 Press OK key to confirm the modification VOLTAGE CALIBRATE Page6 Bypass VOL Bypass voltage calibration Click value columns and it w...

Страница 30: ...NITIAL menu Page1 INITIAL Datalog Page DATA LOG After clicking DATA LOG it will pop up a message board as shown in above screen Touch YES to clear the DATALOG page Touch No to cancel this operation To...

Страница 31: ...Page EEPROM After clicking EEMPROM it will pop up a message board as shown in above screen Touch YES to clear all setting value in EEPROM Touch No to cancel this operation Touch to return to INITIAL...

Страница 32: ...ble CVCF function is disabled The output frequency will synchronize with the bypass frequency within 46 54 Hz for 50Hz system or within 54 64 Hz for 60Hz system Disable is the default setting Bypass F...

Страница 33: ...muted automatically and the UPS will go back to normal mode automatically CHE The UPS will detect the neutral loss or not only when first commission If neutral loss is detected an alarm will be gener...

Страница 34: ...etting This setting is only available for long run model Battery age if battery age is beyond the setting month then the UPS will alarm for reminding The factory default setting is 24 months Battery A...

Страница 35: ...r Advance Maintainer directory After changing UPS type to HV you have to restart the UPS After the UPS is restarted please enter Advance screen and enter Maintainer password It will show SELFTEST sele...

Страница 36: ...P Version DSP version LCD Version DSP version Serial NO The serial number of UPS Rated Information Page1 Rated Information Output Voltage It shows output rated voltage Output Frequency It shows output...

Страница 37: ...ltage range Line FRE Range The acceptable line input frequency range Bypass Voltage Range The acceptable input voltage range for bypass mode Bypass FRE Range The acceptable input frequency range for b...

Страница 38: ...shuts down Battery Numbers It shows battery number 3 2 6 Data Log screen Touch the icon to enter date log page Data log is used to record the warning and fault information of the UPS The record contai...

Страница 39: ...alized the UPS will auto restart in AC mode 2 Turn on the UPS without utility power supply in Battery mode 1 Make sure that the two strings of batteries are connected correctly in order of GND termina...

Страница 40: ...t down automatically to protect the battery This battery discharge protection can be enabled or disabled through LCD menu 6 Test the batteries 1 If you need to check the battery status when the UPS is...

Страница 41: ...he inverter output voltage difference of each UPS is within 1V or less 2 Turn off each UPS Refer to section 3 4 7 Then follow the wiring procedure in section 2 4 3 Remove the cover of parallel share c...

Страница 42: ...UPS and then turn off the system All UPSs will transfer to Bypass mode Remove all the maintenance bypass covers and set the maintenance switches from UPS to BPS position Turn off all the input breaker...

Страница 43: ...ter L2 L3 output line to line short circuited None 66 Inverter current sample abnormal None 19 Inverter L3 L1 output line to line short circuited None 67 Bypass O P short circuited None 1A Inverter L1...

Страница 44: ...04 IP phase abnormal 33 Locked in bypass after overload 3 times in 30 minutes 05 Bypass phase abnormal 34 Converter current unbalanced 07 Over charge 3A Cover of maintain switch is open 08 Low batter...

Страница 45: ...s from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 UPS is overload too long and becomes fault Then UPS shut down automatically Remove excess loads from UPS output...

Страница 46: ...d precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery terminals and the grou...

Страница 47: ...d 5 100 Non linear Load Transfer Time Line Battery 0 ms Inverter Bypass 0 ms When phase lock fails 4ms interruption occurs from inverter to bypass Inverter ECO 10 ms EFFICIENCY AC mode 95 5 Battery Mo...

Страница 48: ...ERS INDONESIA Office PT PROLiNK INTIDATA NUSANTARA Walk In Jl Cideng Barat No 79 Jakarta Pusat 10150 Indonesia Email Support support id prolink2u com MALAYSIA Office FIDA SYSTEMS M SDN BHD Walk In 29...

Отзывы: