30
ELECTRIC
Electric Page 1
Output VOL: Select the output rated voltage.
When UPS is HV system, there are four options, 208V, 220V, 230V and 240V.
When UPS is LV system, there are two options, 120V and 127V.
Output FRE: Select output rated frequency.
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
CVCF Mode (constant voltage and constant frequency function)
Enable: CVCF function is enabled. The output frequency will be fixed at 50Hz or 60Hz according to
setting of “Output Freq.”. The input frequency could be from 46Hz to 64Hz.
Disable: CVCF function is disabled. The output frequency will synchronize with the bypass
frequency within 46~54 Hz for 50Hz system or within 54~64 Hz for 60Hz system. Disable is the
default setting.
Bypass Forbid:
Enable: Bypass Forbid is enabled. It’s not allowed for running in Bypass mode under any
situations.
Disable: Bypass Forbid is disabled. UPS will run in Bypass mode. It is the default setting.
Electric Page 2
Bypass at UPS off: Select the bypass status when manually turning off the UPS. This setting is only
available when “Bypass forbid” is set to “Disable”.
Enable: Bypass enabled. When selected, bypass mode is activated.
Disable: Bypass disabled. When selected, no output through bypass when manually turning off
the UPS.
Bypass Voltage Range: Set the bypass voltage range.