25
Charge Current:
One piece of charger: There are twelve options: 1A, 2A, 3A, 4A, 5A, 6A, 7A, 8A, 9A, 10A, 11A,
12A.
Two pieces of charger: There are twelve options: 2A, 4A, 6A, 8A, 10A, 12A, 14A, 16A, 18A, 20A,
22A, 24A
BATT Number: The total number of installed battery. (It’s required to restart the UPS after setting.) The
setting range is 16 ~ 20. 16 is default setting.
Charger VOL: The setting point of battery float voltage. 13.6V is default setting.
INSTALL
INSTALL Page
System Install Date: Set the date of UPS installation.
Battery Install Date: Set the date of Battery installation.
VOLTAGE CALIBRATE
VOLTAGE CALIBRATE Page1
Bus VOL: BUS voltage calibration. Click value columns and it will pop up
. Then, each click is 0.1% no
matter it’s pressing up or down key
. Press “up” key to increase 0.1% and press “down” key to decrease
0.1%. Press “OK” key to confirm the modification.