23
BATT
Battery setting page
Battery Warning Voltage:
HIGH: High battery warning voltage. The setting range is 14.0V ~ 15.0V. 14.4V is default setting.
LOW: Low battery warning voltage. The setting range is 10.1V ~ 14.0V. 11.4V is default setting.
This parameter setting is related to “Shutdown Voltage” setting. This setting value should be
higher than “Shutdown Voltage” setting.
Shutdown Voltage: If battery voltage is lower than this point in battery mode, UPS will automatically
shut down. The setting range is 10V ~ 12V. 10.7V is default setting.
Battery age: if battery age is beyond the setting month, then the UPS will alarm for reminding. The
factory default setting is 24 months.
Battery AH: Setting battery capacity
OTHERS
OTHERS setting page
Auto Restart:
Enable: After “Enable” is set, once UPS shutdown occurs due to low battery and then utility
restores, the UPS will return to line mode.
Disable: After “Disable” is set, once UPS shutdown occurs and the utility restores, the UPS will
not automatically turn on.
Shutdown Delay: UPS will shut down in setting minutes. The countdown will start after confirming the
pop-up screen.
Restore Delay: UPS will automatically restart in setting minutes after the UPS shuts down.
New Password: Set up new password to enter “ADVANCE
User” menu.