4. Specifications
MODEL
1.2KVA
2.4KVA
CAPACITY
1200 VA / 720 W
2400 VA / 1440 W
INPUT
Voltage
220/230/240 VAC
Voltage Range
170-280 VAC (UPS mode)
90-280 VAC (INV. Mode)
OUTPUT
Voltage Regulation (Batt. Mode)
+/-10%
Transfer Time
20 ms typical
Waveform
Simulated Sine Wave
BATTERY
Battery Voltage
12 VDC
24 VDC
Floating Charge Voltage
13.7DC ± 2%
27.4 VDC ± 2%
Maximum Charge Current
10 A or 20 A
10 A or 20 A
SOLAR CHARGER
Charging Current
30 A
System Voltage
12 VDC
24 VDC
Operating Voltage Range
15~18 VDC
30~32 VDC
Max. PV Array Open Circuit
Voltage
40 VDC
60 VDC
PHYSICAL
Dimension (DxWxH) mm
293 X 231.5 X 82.5
Net Weight (kgs)
2.35
2.55
5. Installation
NOTE:
Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged.
Connect to Utility and Charge
Plug in the AC input cord to the wall outlet. The unit will automatically charge the connected
external battery even though the unit is off.
Connect External Battery
Step 1-
Take away the cover of external battery terminal.
Step 2
- Following battery polarity guide printed near the battery terminal!
Place the external battery cable ring terminal over the battery terminal.
RED cable to the positive terminal (+);
BLACK cable to the negative terminal (-).
WARNING!
Please use the appropriate battery cable. Please refer to
Important Safety
Warnings Section
for the details.
Step 3
- Tight the battery cables with the M5 nuts. Do NOT place anything between the flat
part of battery terminal and the battery cable ring terminal, or overheating may occur.
(See Fig. 1)
Step 4
- Install a DC Breaker in a positive battery line. The
rating of the DC Breaker must be according to the inverter's
battery current (75 Amp). Keep the DC breaker off.
(see Fig. 2)
Step 5
- Connect battery cables to the external batteries. Note:
For the user operation safety, we strongly recommend that you
should use tapes to isolate the battery terminals before you
start to operate the unit.
1) Single battery connection(Refer to Fig. 2):
When using a single battery, its voltage
must be equal to the Nominal DC Voltage of the unit
(see below Table 1).
2) Multiple batteries in series connection(Refer to Fig. 3):
All batteries must be equal
in voltage and amp hour capacity. The sum of their voltages must be equal to the nominal DC
Voltage of the unit.
Fig 3
3) Multiple batteries in parallel connection(Refer to Fig. 4):
Each battery's voltage
must be equal to the Nominal DC Voltage of the unit.
Fig 4
Step 6
- Make sure to connect the polarity of battery side and the unit correctly.
Positive pole (Red) of battery to the positive terminal (+)of the unit.
Negative pole (Black) of battery to the negative terminal (-) of the unit.
Step 7
- Put the covers back to the external battery terminals.
Step 8
- Take the DC breaker on.
Fig. 2
Fig.1