7. Trouble Shooting 

Use the table below to solve minor problems. 

Problem 

LCD/LED/ 

Buzzer

 

Possible Cause 

Solutions 

Utility power is   
normal but 
the unit is in 
battery mode. 

Input voltage 
is displayed as 
0 on the LCD 
and yellow LED 
is on or 
flashing. 

AC input power cord 
is not connected 
well. 

Check AC input power 
connection. 

Input breaker is 
activated. 

Reset the input breaker. 

When power 
fails, the 
backup time is 
shorten. 

Battery low 
alarm issue 
quickly 

Battery voltage is 
too low. 

Charge the unit at least 8 
hours. 

Battery capacity is 
not full even after 
charge the unit for 
at least 8 hours. 

Check the date code of the 
battery. If the batteries are too 
old, replace the batteries. 

When utility 
power is 
normal. 

No LED display 
on the front 
panel 

Battery is not 
connected well. 

Check the external battery 
cable and terminal. Make sure 
all the battery connections to 
the unit are all correct. 

Battery defect.   

Replace the batteries. 

Buzzer beeps 
continuously 
and red LED is 
on. 

LCD display F0 

Output short 
circuited. 

Check if wiring is connected 
well and remove abnormal 
load. 

LCD display F1 

Overload error. The 
inverter is loaded 
with more than 
110% load and time 
is up 

Reduce the connected load by 
switching off some equipment. 

LCD display F2 

The battery voltage 
is too low 
(<1.4V/Cell) 

1. Re-charge battery. 
2. Replace battery. 

LCD display F3 

Output high 
(Inverter voltage is 
higher than 253Vac) 

Return to repair center 

LCD display F4 

The relay had been 
damaged during the 
AC short circuit 

Return to repair center. 

LCD display F5  Fan fault 

Replace the fan 

If there is any abnormal situations occur, which doesn't list above, please call the service 
people immediately for professional examine. 
 

Содержание IPS1200A

Страница 1: ... The unit is designed for indoor use Do not expose this unit to rain snow or liquids of any type CAUTION To reduce risk of injury only use qualified batteries from qualified distributors or manufacturers Any unqualified batteries may cause damage and injury Do NOT use old or overdue batteries Please check the battery type and date code before installation to avoid damage and injury WARNING It s ve...

Страница 2: ...ompartment CAUTION Use insulated tools to reduce the chance of short circuit when installing or working with the inverter the batteries or other equipments attached to this unit CAUTION For battery installation and maintenance read the battery manufacturer s installation and maintenance instructions prior to operating Personnel Precaution CAUTION Careful to reduce the risk or dropping a metal tool...

Страница 3: ...e Please refer to Important Safety Warnings Section for the details Step 3 Tight the battery cables with the M5 nuts Do NOT place anything between the flat part of battery terminal and the battery cable ring terminal or overheating may occur See Fig 1 Step 4 Install a DC Breaker in a positive battery line The rating of the DC Breaker must be according to the inverter s battery current 75 Amp Keep ...

Страница 4: ...connection Refer to below table Model Best Vmp Vmp range 1 2KVA 15Vdc 15V 18V 2 4KVA 30Vdc 30V 32V Note Vmp panel max power point voltage The PV charging efficiency is maximized while PV system voltage is close to Best Vmp Maximum PV module numbers in Series Vmpp of PV module X pcs Best Vmp of Inverter or Vmp range PV module numbers in Parallel Max charging current of inverter Impp Total PV module...

Страница 5: ... Off Battery fully charged at power off and Off flashing every 11 sec Battery mode Battery weak and will flash every 2 second Sounding every 1 sec None weak battery Off Fault mode Fault code will be displayed Short fault F0 Overload fault F1 Battery bad F2 High output voltage F3 Main Relay Stick F4 Fan fault F5 Continuously sounding for 30 min and then alarm off The unit is overload The mark will ...

Страница 6: ...nel Battery is not connected well Check the external battery cable and terminal Make sure all the battery connections to the unit are all correct Battery defect Replace the batteries Buzzer beeps continuously and red LED is on LCD display F0 Output short circuited Check if wiring is connected well and remove abnormal load LCD display F1 Overload error The inverter is loaded with more than 110 load...

Отзывы: