BLOWN
Fuse blown or removed
PSU Temp:
HEATING
High Temperature
OK
Normal Temperature
If one of the following indications appears, consult the list of faults:
PSU COMMUNICATION LOSS
Communication fault with PSU
FLASH FAILURE
PSU Microprocessor fault
WATCHDOG RESET
PSU Microprocessor fault
The
Auxiliary power supply
menù allows you to view the status of backup power supply connected to the
buffer batteries:
Aux power status:
DISABLED
Disabled (Disablement)
FAULT
Faulty
OK
Running
Battery Status:
ABSENT
Battery pack removed
SHORT
Battery pack in short-circuit
REVERSE
Battery pack reverse-connected
OVERCURRENT
Current protection active, battery pack disconnected
CHARGE LOW
Battery pack charge low
IN USE
Battery pack in use
Z TEST
Battery pack impedance test running
ON CHARGE
Battery pack on charge
IDLE
Battery pack at rest
Batt temp:
PROBE SHORT
Battery pack temperature probe in short circuit
PROBE OPEN
Battery pack temperature probe open or removed
OVERTEMP
Overheating of the battery pack; temperature out of range
UNDERTEMP
Battery pack temperature below threshold.
OK
Battery pack temperature correctly in range.
Batt Z:
(Battery pack impedance)
ERROR
Battery pack impedance out of range, batteries to be replaced
WARNING
Battery pack impedance near the error threshold
OK
Battery pack impedance correctly in range.
NOTE:
If the temperature of the battery pack is in error or the probe is not working, charging and
impedance testing are suspended.
For completeness, the measured voltage value of the battery pack in volts is indicated.
If one of the following indications appears, consult the list of faults:
PSU COMMUNICATION LOSS
Communication fault with PSU
FLASH FAILURE
PSU Microprocessor fault
WATCHDOG RESET
PSU Microprocessor fault
The
Battery charger
menù
allows you to view the status of the battery pack charger.
Charger status:
DISABLED
Disabled (Disablement)
FAULT
Faulty
OK
Properly functioning
Activity:
GENERAL FAULT
Charger circuit faulty
ON CHARGE
Charging of battery pack
Z TEST
Battery pack impedance test running
CHARGER TEST
Charger circuit test running
Содержание AE604
Страница 2: ...AE604 INTEGRATED VOICE ALARM SYSTEM EN54 16 EN54 4 ...
Страница 40: ...40 USRMAN_AE604EN_REV002 MECHANICAL DIMENSIONS ...
Страница 42: ...42 USRMAN_AE604EN_REV002 ...
Страница 43: ...43 ...
Страница 44: ...44 USRMAN_AE604EN_REV002 ...
Страница 46: ...46 USRMAN_AE604EN_REV002 ...
Страница 47: ...www proel com ...