-25-
156.0 [6.14 ]
Expansion Unit Interface
This interface is used to connect an expansion unit that can transmit data over
a Fieldbus or similar type of network.
Tool Connector
Connects a Data Transfer Cable or bar code reader.
Connect the GLC to a serial printer via the Data Transfer Cable and
a User-created conversion cable.
GLC2300 Series User Manual
Ethernet Interface
This interface complies with the IEEE802.3 standard for Ethernet (10BASE-T)
connections. This interface uses an RJ-45 type modular jack (8 points).
CF Card Interface
This slot accepts a CF Card.
• Before installing the GLC into a cabinet or panel, check that
the installation gasket is securely attached to the unit.
• A gasket which has been used for a long period of time may
have scratches or dirt on it, and could have lost much of its
dust and drip resistance. Be sure to change the gasket peri-
odically (or when scratches or dirt become visible).
Confirm the Installation Gasket's Positioning
It is strongly recommended that you use the gasket. It absorbs vibration in
addition to repelling moisture.
Place the GLC on a level surface with the display panel facing downward.
Check that the GLC’s installation gasket is seated securely into the gasket’s
groove, which runs around the perimeter of the panel’s frame.
5
Installation
Gasket
Rear face
Create a Panel Cut and insert the GLC into the panel from the front
Unit: mm [in]
+1
0
+0.04
0
under 4-R3
Panel
Panel thickness:
1.6mm[0.06in] to
5.0mm[0.20in]
GLC
Panel
123.5 [4.86 ]
+0.04
0
+1
0