ACTIVE ALARMS
If an alarm event occurs, it is displayed on the message bar on the Main Screen. A flashing alarm bell
is also displayed.
Possible alarms include:
#
DISPLAY
DEFINITION
FIX
0
HIGH LEVEL XDCR
Level in the wet well has exceeded the High
Level Set point
Check pump operation, check in flow, check
level transducer
1
MAX RUN TIME
Pump running longer than allowable Run time
Check pump operation, check in flow, check
level transducer
2
HIGH LEVEL FLOAT
High level float is ON (up)
Check pump operation, check in flow, check
level transducer
3
LOW LEVEL FLOAT
Low level float is OFF (down)
Check transducer
4
HIGH AMPS
Pump amps higher than expected (after time
delay)
Check pump, check voltage
(low or imbalance)
5
DRY RUN
Pump amps lower than expected for time
delay
Check transducer, check low level float,
check pump
6
LEVEL SENSOR OPEN
Transducer signal is less than 4mA
Check transducer connection, check trans-
ducer and vent tube
7
LEVEL SENSOR SHORT
Transducer signal is more than 20mA
Check transducer
8
P1 OL/OT
Pump 1 Overload trip or Over temp trip
Check pump operation, clogging
9
P2 OL/OT
Pump 2 Overload trip or Over temp trip
Check pump operation, clogging
10
STOP FLOAT FAIL
Stop float out of sequence
Check float tree
11
START FLOAT FAIL
Start float out of sequence
Check float tree
12
LAG FLOAT FAIL
Lag float out of sequence
Check float tree
13
CURRENT SENSOR OPEN
Current sensor signal is less than 4mA
Check transducer connection, check
transducer
14
POWER FAIL
Power loss or Phase loss to the control panel
Check incoming power and phase loss
monitoring setting (if used)
15
ILLEGAL ENTRY
Unauthorized personnel are tampering with
the control panel
Control access to the control panel