SYSTEM (ADVANCED SETUP)
The Station View
™
controller can be configured to operate using a 4-20mA level transducer with 2
backup float switches or with 4 float switches and no transducer. See the electrical schematic for
sensor connections.
Example: 0-10psi range level transducer = 0-23.0 ft. (1psi = 2.30 ft.) Set 20mA=23.0 ft
Some transducers are already calibrated in ft. (Max value for 20mA is 99.9 ft)
When using a submersible pressure transducer, 0.0 ft. represents the level at the bottom of the
transducer and not the wet well. If the transducer is mounted 2.0 ft off the bottom of the tank, set
the offset = 2.0 ft. (Max value -10.0~10.0 ft)
SENSOR (ADVANCED SETUP)
Entering the measuring range of the level transducer. This data is provided with the level transducer.
PRIMEX
®
12 Station View
™
Controller User Manual