ULTRASUITE ARRAY - Manual
ULTRASUITE ARRAY
INSTALLATION INSTRUCTIONS
Step 3:
Wire the low voltage side of each remote driver cabinet according to appropriate wiring diagrams.
NOTE:
Make sure that the wiring identification mark on the luminaire, wire lead, cord grip and the terminal block connection match.
NOTE:
Wiring should be carried out by a certified electrician and meet national and local electrical codes.
WIRING DIAGRAM FOR ONE LED DRIVER
Initials
Completion date
Factory order no
Operator
Sch date
Part qty
Comment/Tag
Issued date
Blank qty
(mm/dd/
yyyy)
Sheet
of
Revision
Description
Drawing no.
Date
Status
Drawn by
Scale
2018-09-07
USA
WIRING DIAGRAM - FIELD CONNECTIONS
269685
0
1
6
Solid Edge
KVR
NTS
Rev Description
ECN
Date (y/m/d) By
Print Date: 2018-09-07 - 269685.dft
Print Date: 2018-09-07 - 269685.dft
Ne
tw
or
k
File
L
o
ca
tio
n:
T
:\C
rit
ic
al
En
vir
o
nm
en
ts
\U
SA
\M
an
uf
ac
tur
in
g
De
tai
ls
\S
tan
dar
d\
26
96
85
.df
t
(-
)
(+
)
L
L
DH
DH
N
N
G
G
G N DH L
(+)
(-)
(+)
(-)
DRIVER 1
G
G
L
DH
N
G
LINE/CONTROL
120-277
~
FROM DIMMER SWITCH
24 VDC
LOW VOLTAGE
TO
DIFFUSER/LED
MODULE
JUNCTION BOX
HVTB
1
2
LEGEND
G - GROUND
N - NEUTRAL
DH - DIMMED HOT
L - SWITCHED HOT
(+) - LED +
(-) - LED -
HVTB - HIGH VOLT TERMINAL BLOCK
LVTB - LOW VOLT TERMINAL BLOCK
-001
1 DRIVER
DASH NO.
DESCRIPTION
LINE LEGEND
FACTORY ELECTRICAL WIRING
FIELD ELECTRICAL WIRING
WIRE GAGE
LENGTH (FT)
18 AWG
15 FT
16 AWG
25 FT
14 AWG
45 FT
12 AWG
70 FT
10 AWG
115 FT
8 AWG
180 FT
WIRING NOTES
1. USE COPPER 75 C MIN. RATED WIRE FOR FIELD CONNECTION SUPPLY.
2. USE COPPER 80 C MIN. RATED PLENUM RATED WIRE FOR LOW VOLTAGE
FIELD CONNECTION.
(SEE TABLE BELOW FOR RECOMMENDED WIRE GAGE AND LENGTHS)
LVTB
Initials
Completion date
Factory order no
Operator
Sch date
Part qty
Comment/Tag
Issued date
Blank qty
(mm/dd/
yyyy)
Sheet
of
Revision
Description
Drawing no.
Date
Status
Drawn by
Scale
2018-09-07
USA
WIRING DIAGRAM - FIELD CONNECTIONS
269685
0
1
6
Solid Edge
KVR
NTS
Rev Description
ECN
Date (y/m/d) By
Print Date: 2018-09-07 - 269685.dft
Print Date: 2018-09-07 - 269685.dft
Ne
tw
or
k
File
L
o
ca
tio
n:
T
:\C
rit
ic
al
En
vir
o
nm
en
ts
\U
SA
\M
an
uf
ac
tur
in
g
De
tai
ls
\S
tan
dar
d\
26
96
85
.df
t
(-
)
(+
)
L
L
DH
DH
N
N
G
G
G N DH L
(+)
(-)
(+)
(-)
DRIVER 1
G
G
L
DH
N
G
LINE/CONTROL
120-277
~
FROM DIMMER SWITCH
24 VDC
LOW VOLTAGE
TO
DIFFUSER/LED
MODULE
JUNCTION BOX
HVTB
1
2
LEGEND
G - GROUND
N - NEUTRAL
DH - DIMMED HOT
L - SWITCHED HOT
(+) - LED +
(-) - LED -
HVTB - HIGH VOLT TERMINAL BLOCK
LVTB - LOW VOLT TERMINAL BLOCK
-001
1 DRIVER
DASH NO.
DESCRIPTION
LINE LEGEND
FACTORY ELECTRICAL WIRING
FIELD ELECTRICAL WIRING
WIRE GAGE
LENGTH (FT)
18 AWG
15 FT
16 AWG
25 FT
14 AWG
45 FT
12 AWG
70 FT
10 AWG
115 FT
8 AWG
180 FT
WIRING NOTES
1. USE COPPER 75 C MIN. RATED WIRE FOR FIELD CONNECTION SUPPLY.
2. USE COPPER 80 C MIN. RATED PLENUM RATED WIRE FOR LOW VOLTAGE
FIELD CONNECTION.
(SEE TABLE BELOW FOR RECOMMENDED WIRE GAGE AND LENGTHS)
LVTB