INSTALLATION INSTRUCTIONS
Remote Driver Cabinet Mounting and Installation
WARNING! SHOCK HAZARD! MAY RESULT IN SERIOUS INJURY OR DEATH. TURN OFF POWER AT CIRCUIT
BREAKER BEFORE INSTALLING THE UNIT.
• Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and
standards.
• When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities.
Step 1:
Snap chalk line on the floor to outline locations and sizes of module assembly sections.
Step 2:
Unpack module assembly sections and lay them out on the floor as per the job specific submittal package and determine
remote driver cabinet mounting location. Ensure adequate wire length is available to wire to the remote driver cabinet. Refer to
page 3 for luminaire mounting and installation and page 11 for electrical connections.
Step 3:
Mount remote driver cabinet(s) to the wall using the six mounting holes in the bottom of the remote driver cabinet (fig. 20).
Remote driver cabinet weighs 120lbs, ensure adequate mounting techniques/methods are used. This product must be installed in
accordance with the applicable installation codes as required.
NOTE:
Remote driver cabinet must be surface mounted on the wall with the louvers facing up and down (fig. 20)
NOTE:
Louvers or slots in remote driver cabinet must be kept clear to ensure proper airflow through the cabinet. Failure to do so
may shorten the life expectancy of the remote drivers.
Step 4:
Repeat above steps until all remote driver cabinets have been installed.
NOTE:
Remote driver cabinets must have a minimum of 6 in. clearance on all sides (fig. 21).
FIGURE 20: REMOTE DIVER CABINET MOUNTING
LOCATIONS
FIGURE 21: MULTIPLE REMOTE DRIVER CABINETS
INSTALLED