VV
22 | VV – Manual | AntecControls.com
Valve Pressure Switch (VPS)
Valve Pressure Switch (VPS) is an adjustable, pressure-actuated electrical switch that makes or breaks an electrical circuit at a
predetermined pressure.
Overview
See the VPS Product Submittal on AntecControls.com for specifications and dimensions.
Options
Installation
The VPS is provided factory installed when ordered with a Venturi Valve. For any field mounted applications, see instructions
below.
Valve Pressure Switch (VPS)
Model:
Features:
VPS
•
Factory set to actuate on a pressure rise of 0.30 in.w.c. for low pressure Venturi
Valves and 0.60 in.w.c. for medium pressure Venturi Valves
•
Adjustable setpoint range
STEP 1
Using self-tapping screws, mount the VPS to a location within the valve’s controls enclosure. Make sure there is adequate room around the VPS to make
the electrical connections and connect the pressure tubing.
STEP 2
Connect the pressure tubing from the Hi side of the Venturi Valve to the Hi port on the pressure switch.
STEP 3
Connect the pressure tubing from the Lo side of the Venturi Valve to the Lo port on the pressure switch.
STEP 4
Connect the NO or NC (depending on the application) and COM wires from the VPS to the device being used to monitor the valve pressure.
Содержание Antec Controls VENTURI VV Series