Slip-Connection Venturi Valve Mounting Instructions
The instructions below are detailed for Aluminum Venturi Valves only. Do not use screws for Phenolic or Kynar coated valves.
Flange-Connection Venturi Valve Mounting Instructions
STEP 1
Mount the Venturi Valve by slipping both the inlet and the discharge one inch (1”) into the
appropriately sized ductwork.
STEP 2
Fasten the Venturi Valve to the ductwork using six (6) sheet metal screws per slip
connection.
STEP 3
Seal the ductwork using duct sealer.
STEP 1
Align the duct flange holes with the venturi flange holes and fasten using a bolt, lock washer
and nut. Fasten every hole to reduce airflow leakage.
NOTE:
It is recommended to use a duct sealant or gasket between the valve flange and the
ductwork flange.
CAUTION
Instructions above are for slip valves without drawband
clamps. For information on installing slip valves with
drawband clamps, please see the
CAUTION
Instructions above are for flanged valves without
companion flanges. For information on installing flanged
valves with companion flanges, please see the