VV
15 | VV – Manual | AntecControls.com
Electric Coils (VVEC)
Electric Coils (VVEC) are devices installed with Venturi Valves that control room environment by heating the air moving through
the valve. The VVEC operates using standard building electrical power and is designed to optimize heat transfer.
Overview
See the VVEC Product Submittal on AntecControls.com for specifications and dimensions of the options below.
Options
Electric Coils
Model:
Features:
VVEC
•
Automatic reset thermal cut-out
•
Manual reset thermal cut-out
•
Air flow switch
•
20 Gauge galvanized steel, mechanically sealed, leak
resistant construction
•
SCR Controls – 2 to 10 VDC
Before Installation
1.
Check for shipping damage to heater assembly including, but not limited to, ceramic coil clips and wire damage. If damage is
found, do not power up heater, file claim with carrier and/or replace heater.
2.
Check electrical specification label to ensure proper voltage/current ratings.
3.
Before wiring, review and adhere to all local building codes, ordinances and the National Electric Code, pertaining to
installation of the equipment.
4.
Determine if the unit is field flippable between left and right handling.
5.
If mercury contactors are included, ensure the arrow on the label is pointed upward.
NOTES:
1.
To maintain ETL certification, electric coils must only be installed as they have been marked on the installation label provided
on the door of the electric coil control panel. (Installation Label PIC)
2.
A minimum static pressure of 0.20 in.w.c is required for stable operation with electric heater controls.
CAUTION
When installing, do not handle the unit by the inlet
velocity sensor. Ensure any packing material is
removed from the inside of the unit.
Содержание Antec Controls VENTURI VV Series
Страница 1: ...VENTURI VALVE VV Series MANUAL v113...