..\Manuals\RCI-800-MDM rev.C.doc
Page 11 of 15
AI % Dialing
Determines if a specific amount of change on
A
nalog
I
nput x (x=1,2,..8) causes a call to be
placed. If this unit is a remote, then a call will
be placed to the host. If this unit is a host then
a call will be placed to the remote that
corresponds to this input channel.
The amount of change required before a call
is placed is expressed as a percentage of full-
scale signal. Be aware that a full-scale signal is
from 0-20mA. Hence a 5% change would be
1mA. A call will be placed if the input signal
either rises or falls more than the specified
percentage compared to the signal level at the
last call.
Allowable values
:
0 = no call for percent change
1-50 = call on % change from NORMAL
Phone Numbers
HOST
The phone number of the host. It
may be up to 15 characters long and may
contain only digits and commas (,). A comma
inserts a 2 second pause into the dialing
sequence which may be necessary if the unit
is on a PBX system where it needs to dial a
number for an outside line and then wait
before it dials the rest of the phone number.
REMOTE1
The phone number for REMOTE 1.
The same rules apply as for the HOST
:
:
REMOTE8
The phone number for REMOTE 8.
The same rules apply as for the HOST