DI Status Dialing
Determines whether or not a call will be
initiated when a
D
igital
I
nput changes its status.
If
NO
is selected for an input, no call will be
made if its status changes. However, if
YES
is
selected, whenever that digital input switches
from open-to-closed or closed-to-open, a call
will be made.
If this unit is a remote, then a call will be
placed to the host. If this unit is a host then a
call will be placed to the remote that
corresponds to this input channel.
Allowable values
:
NO = no call on status change
YES = call on status change
AI Level Dialing
Determines if a HIGH/LOW level on
A
nalog
I
nput x (x=1,2,..8) causes a call to be placed. If
this unit is a remote, then a call will be placed to
the host. If this unit is a host then a call will be
placed to the remote that corresponds to this
input channel.
A HIGH level occurs when the input value
rises above this parameter. When the input
level drops below 2% below this parameter the
level is considered NORMAL and another call
will be placed automatically.
A LOW level occurs when the input value falls
below this parameter. When the input level
rises above 2% above this parameter the level
is considered NORMAL and another call will be
placed automatically.
Allowable values
:
0 = no call on HIGH and/or LOW level
1-65535 = call on HIGH and/or LOW level
and call when HIGH and/or LOW level
returns to NORMAL
The parameter is calculated as follows:
(where
SETPOINT
is between 4-20
mA
)
×
−
=
65535
16
4
)
(
mA
mA
mA
SETPOINT
PARAMETER