AUTODIAL

  The auto-dial time interval in 

minutes.  If this parameter is set to 0 then the 
unit will NOT automatically initiate a call and will 
call only when a DI or AI status changes (see 
below).  If this parameter is set to a value 
greater than 0 then the unit will place a call 
automatically in this time interval. 

     

Allowable values

:  

        

0 = no auto-dial  

        1-65535 auto-dial interval (min.) 
 

REDIAL

   Number of times the unit will attempt a 

re-dial if the previous dial failed to establish a 
connection (because of busy signal, reorder 
signal, etc.). If the unit does not establish a 
connection after the set number of redials it 
suspends the re-dial procedure for the specified 
Redial Interval minutes.  New events that will 
require a call to be placed will re-initiate the 
dialing procedure. 

     

Allowable values

:  

        

0 = re-dial until successful  

        1 thru 9 number of re-dials 
 

REDIAL PAUSE

   Time interval, in seconds, the 

unit waits between re-dials.  To prevent ongoing 
contention between units it is recommended 
that every unit in a system be assigned a 
different PAUSE interval.  That way if two units 
happen to call at the same time, they wait 
different intervals before re-dialing.     

     

Allowable values

:  

        

10-255 = re-dial interval in seconds    

              (note the 10 second minimum)

 

 

REDIAL INTERVAL

   Time interval, in minutes, 

the unit waits between each redial cycle. The 
unit will continue to execute redial cycles until a 
connection is established.       

 

Allowable values

:  

        

0-65535 = re-dial interval in minutes    

 

RINGS  

The number of rings before the unit 

answers an incoming call. 

     

Allowable values

:  

        

0 = never answer a call 

        1 thru 9 = rings before answer

  

 
 
 
 
 

 

 

 

  
 

REDIAL FAIL

   Number of redials executed 

before the fail contact is activated.    

     

Allowable values

:  

        

0 = continuous 

    1 thru 9 = attempts before fail signal 

   Redial Example Diagram

 

 

Содержание RCI-800-MDM

Страница 1: ...0 5336 Model Serial Function XXX MDM Modem Dial Up Communication RCI 800 XXX If special or required 8 Dry Contact and 8 Analog Inputs Input Remote Control Signal Interface XXX SER RS 232 485 Output 8 Form C Contact and 8 Analog Outputs XXX FSK Leased Line XXX RF2 2 4 Ghz Wireless XXX RF9 900 Mhz Wireless Power 24 VDC 117VAC 50 60Hz 240 VAC 50 60Hz ...

Страница 2: ...oducts or all non standard products may not be returned for restocking Pribusin Inc warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions of use and service and will replace any component found to be defective on its return to Pribusin Inc transportation charges prepaid within one year of its original purchase Pribusin Inc will extend...

Страница 3: ...X system make sure it can accept analog modem transmissions Serial systems connect via standard modem cable Standard Features Bi directional Communication using Phone Line Dial Out Programmable for Status Setpoint Change Incremental Signal Change and Timed Interval Point to Point or Host to Multi Point Operation 8 Dry Contact and 4 Analog Inputs 8 C Relay Contacts and 4 Analog Outputs Configurable...

Страница 4: ...log 8 Contact 8 Analog 8 Contact 8 Analog 8 Contact 2 Analog 2 Contact 2 Analog 2 Contact 4 Analog 4 Contact 4 Analog 4 Contact OR 8 Analog 8 Contact 8 Analog 8 Contact 8 Analog 8 Contact 8 Analog 8 Contact 15 25 13 25 6 5 www pribusin com info pribusin com CANADA Pribusin Inc 101 Freshway Dr Unit 57 Concord Ontario L4K 1R9 Ph 905 660 5336 Fx 905 660 4068 USA Pribusin Inc 743 Marquette Ave Muskego...

Страница 5: ......

Страница 6: ......

Страница 7: ...0VAC and protected by a 500mA SLOBLO fuse It can be wired for 240VAC operation by removing de soldering power jumpers J1 J2 and installing soldering jumper J3 When changing the RCI 800 to 240VAC power make sure to change the fuse to half of its value 250mA This is important since at 240VAC the RCI 800 requires only half the current as if it were powered from 120VAC Proper protection is only achiev...

Страница 8: ... draw up to 125mA A total of 1A is available to power up to 8 field transmitters On a 2 wire connected input the field transmitter receives power from the RCI 800 and superimposes the signal onto the power return path A maximum of 20mA will flow in such a connection Make sure to consult the field transmitter manual to determine how to connect it to the RCI 800 Outputs The RCI 800 has eight form C ...

Страница 9: ...d set it aside leaving it connected to the analog input output board via the 4 conductor I O cable Turn the power on and insert jumper H1 8 on the main circuit board and turn the OUTPUT CALIB trim pot for a particular output until that output reads 20mA Turn the power off again before re assembling the unit If both jumpers are IN the analog and contact inputs are passed straight through to the ana...

Страница 10: ... depending on jumper H1 4 the outputs will change at a rate determined by the jumper H1 6 2 The low end of the output value can be selected to be either 0mA or 4ma depending on jumper H1 5 This setting only applies to the output value during a fail condition when the outputs are selected to ramp to 0 If jumper H1 5 is out the outputs will ramp to 0mA if it is in they will ramp to 4mA The setting o...

Страница 11: ... is a change of status at one site or the other Both units can be programmed to operate in the Answer and Originate mode thus providing bi directional status change updates Modem configuration is done via a bank of DIP switches The switches are located on the communications board just to the left of the telephone jack They are a slanted rocker type that flips up for OFF and down for ON In Answer O...

Страница 12: ...board has one bank of 8 position DIP switches SW1 SW1 8 controls the mode of operation of the modem Answer Only Mode Configuration To make an RCI 800 MDM operate as an Answer Only unit make sure that SW1 8 is flipped DOWN Set the number of rings before the RCI 800 MDM is to answer using SW1 1 2 3 These switches are binary encoded as shown in the chart to the right If the RCI 800 MDM is to ignore a...

Страница 13: ... especially important in multi remote systems Allowable values 0 Host 1 thru 8 Remote1 thru Remote8 REMOTES Number of remotes in the system In a multi remote system this tells the host how many remotes it has to call when it initiates a call Allowable values 1 thru 8 HOST CHANNELS Number of channels to be used on the host All channels of all remotes in any system must add up to the number of chann...

Страница 14: ...e dialing procedure Allowable values 0 re dial until successful 1 thru 9 number of re dials REDIAL PAUSE Time interval in seconds the unit waits between re dials To prevent ongoing contention between units it is recommended that every unit in a system be assigned a different PAUSE interval That way if two units happen to call at the same time they wait different intervals before re dialing Allowab...

Страница 15: ... and output settings after a power failure Allowable values NO NO dial at power up YES DIAL in PAUSE seconds after power up TIMEOUT Time interval in seconds to wait for called unit to answer If the called unit does not answer in this time the call is considered unsuccessful Allowable values 10 255 wait interval in seconds note the 10 second minimum COM Select the COM Port to which the RCI MDM is c...

Страница 16: ... 1 2 8 causes a call to be placed If this unit is a remote then a call will be placed to the host If this unit is a host then a call will be placed to the remote that corresponds to this input channel A HIGH level occurs when the input value rises above this parameter When the input level drops below 2 below this parameter the level is considered NORMAL and another call will be placed automaticall...

Страница 17: ...ill be placed if the input signal either rises or falls more than the specified percentage compared to the signal level at the last call Allowable values 0 no call for percent change 1 50 call on change from NORMAL Phone Numbers HOST The phone number of the host It may be up to 15 characters long and may contain only digits and commas A comma inserts a 2 second pause into the dialing sequence whic...

Страница 18: ...until the unit is configured properly We suggest that you download the configuration data again after you have uploaded it to make sure that the RCI 800 MDM accepted it properly Upon completion turn the power switch OFF again remove jumper H6 1 move jumpers H5 back to the NORM position disconnect the serial cable and finally turn the power switch back on Download Configuration Data 1 Make sure you...

Страница 19: ... Answer and Originate Mode The file is very simple in structure Modifications can be made easily with a text editing program however care must be taken to adhere to a few constraints 1 The first line of the configuration file must read RCI MDM The is very important During a configuration file upload the tell the RCI 800 MDM that a configuration file is being sent 2 Any line starting with a semi co...

Страница 20: ...e 14 of 15 Above is the header portion of the configuration file It serves as a quick reference and it is sent out by the RCI 800 MDM every time the configuration data is downloaded It immediately precedes the actual configuration data ...

Страница 21: ... Manuals RCI 800 MDM rev C doc Page 15 of 15 Above is the parameter portion of the configuration file This is where changes can be made using a text editing program ...

Отзывы: