Installation - Domestic Piping
Temperature & Pressure (T&P) Relief Valve
To reduce risk of excessive pressures and tem-
peratures in the water heater, install tempera-
ture and pressure protective equipment
required by local codes, but no less than a com-
bination temperature and pressure relief valve
certified by a nationally recognized testing lab-
oratory that maintains periodic inspection of
production of listed equipment or materials, as
meeting the requirements for Relief Valves and
Automatic Gas Shutoff Devices for Hot Water
Supply Systems, ANSI Z21.22. This valve must
be marked with a maximum working pressure
of the water heater.
• The Excellence water heater must be protected
with a T&P relief valve.
• Size the Excellence T&P relief valve by the
following specifications, unless they conflict
with local codes: 3/4” NPT with an AGA
Rating of 100,000 BTU/hr (Watts 100XL-8 or
equivalent).
For proper operation of the T&P and to pre-
vent the T&P from activating due to boiler
water temperature, use a T&P relief valve
with extended element. A 8” minimum
length is recommended.
Standard Installation
• Install T&P relief valve in the
Auxiliary
con-
nection located behind the air vent on the top of
the water heater as shown Fig. 2 page 8.
Commonwealth of Massachusetts Installation
Follow this procedure for jurisdictions requiring a
vacuum breaker to be installed on the domestic
cold water inlet.
• Install the T&P in the run (straight through leg)
of a tee located at the domestic hot water out-
let. Use a long element T&P relief valve, as
shown in Fig. 3 page 8.
T&P Relief Valve Discharge Piping
T&P relief valve discharge piping must be:
- made of material serviceable for tempera-
tures of 250ºF or greater.
- directed so that hot water flows away from
all persons.
- directed to a suitable place for disposal.
- installed so as to allow complete draining
of the T&P relief valve and discharge line.
T&P relief valve discharge piping
must not
be:
- excessively long. Using more than 2
elbows or 15 feet of piping can reduce dis-
charge capacity.
- directly connected to a drain. Terminate
discharge piping within 6” from drain.
Refer to local codes.
- plugged, reduced or restricted.
- subject to freezing.
Do not install any valve between T&P relief
valve and tank connection or on T&P relief
valve discharge piping. Do not plug T&P
relief valve or discharge piping. Improper
placement and piping of T&P relief valve
can cause severe personal injury, death or
substantial property damage.
WARNING
NOTICE
CAUTION
Содержание Excellence
Страница 26: ...19 Boiler Piping Fig 6 Piping Component Legend ...
Страница 36: ...29 Internal Wiring Fig 19 PRESTIGE Excellence Boiler Factory Wiring ...
Страница 40: ...33 External Wiring Diverter Valve CH 1 Pump AUX Fig 20 Multiple Zone Field Wiring Using Zone Valves ...
Страница 41: ...34 External Wiring Diverter Valve CH 1 Pump AUX Fig 21 Multiple Zone Field Wiring using Zone Circulators ...
Страница 112: ...Water Heater Specifications 22 Performance ...
Страница 113: ...Notes ...